Cut Sheet

© 2014 CME Wire and Cable, Inc. All Rights Reserved.July 28, 2017
CME Wire and Cable | 495 Horizon Drive NE, Suite 100, Suwanee, Georgia 30024 | www.cmewire.com | 770.623.0001
QI
®
THHN/THWN-2 Copper, PVC Insulated, Nylon Jacket, 600 V
Technical Data continued
QI
®
THHN/THWN-2 600 V, Copper Conductors
Size
Number
of Wires
Nominal Thickness
Nominal
Diameter
Conductor
Area Ampacity*
Nominal
Mass
Standard Packaging
AWG or
kcmil mm
2
PVC (in) Nylon (in)
in in
2
60 °C 75 °C 90 °C lb/kft
14
2.08 1 0.015 0.004 0.102 0.0082 15 15 15 16
500' (only in 2000' cartons) and 2500' reel
12
3.31 1 0.015 0.004 0.119 0.0111 20 20 20 23
500' (only in 2000' cartons) and 2500' reel
10
5.26 1 0.020 0.004 0.150 0.0177 30 30 30 37
500' (only in 2000' cartons) and 2500' reel
14
2.08 19 0.015 0.004 0.112 0.0098 15 15 15 17
500' (only in 2000' cartons) and 2500' reel
12
3.31 19 0.015 0.004 0.131 0.0134 20 20 20 25
500' (only in 2000' cartons) and 2500' reel
10
5.26 19 0.020 0.004 0.164 0.0211 30 30 30 39
500' (only in 2000' cartons) and 2500' reel
8
8.37 19 0.030 0.005 0.213 0.0356 40 50 55 61
500’, 1000’, 2500’, 5000’, or cut reels
6
13.30 19 0.030 0.005 0.249 0.0487 55 65 75 97
500’, 1000’, 2500’, 5000’, or cut reels
4
21.20 19 0.040 0.006 0.318 0.0794 70 85 95 154
500’, 1000’, 2500’, 5000’, or cut reels
3
26.70 19 0.040 0.006 0.346 0.0940 85 100 110 191
500’, 1000’, 2500’, 5000’, or cut reels
2
33.60 19 0.040 0.006 0.378 0.1122 95 115 130 236
500’, 1000’, 2500’, 5000’, or cut reels
1
42.40 19 0.050 0.007 0.435 0.1486 110 130 150 301
500’, 1000’, 2500’, 5000’, or cut reels
1/0
53.50 19 0.050 0.007 0.474 0.1765 125 150 170 373
500’, 1000’, 2500’, 5000’, or cut reels
2/0
67.40 19 0.050 0.007 0.518 0.2107 145 175 195 463
500’, 1000’, 2500’, 5000’, or cut reels
3/0
85.00 19 0.050 0.007 0.568 0.2534 165 200 225 576
500’, 1000’, 2500’, 5000’, or cut reels
4/0
107.00 19 0.050 0.007 0.624 0.3058 195 230 260 718
500’, 1000’, 2500’, 5000’, or cut reels
250
127.00 37 0.060 0.008 0.678 0.3610 215 255 290 853
500’, 1000’, 2500’, 5000’, or cut reels
300
152.00 37 0.060 0.008 0.730 0.4185 240 285 320 1012
500’, 1000’, 2500’, 5000’, or cut reels
350
177.00 37 0.060 0.008 0.777 0.4742 260 310 350 1170
500’, 1000’, 2500’, 5000’, or cut reels
400
203.00 37 0.060 0.008 0.821 0.5294 280 335 380 1334
500’, 1000’, 2500’, 5000’, or cut reels
500
253.00 37 0.060 0.008 0.902 0.6390 320 380 430 1648
500' 1000', 2500' or cut reels
600
304.00 61 0.070 0.009 1.024 0.8235 355 420 475 1991
500' 1000', 2500' or cut reels
750
380.00 61 0.070 0.009 1.126 0.9958 400 475 535 2474
500' 1000', 2500' or cut reels
1000
507.00 61 0.070 0.009 1.275 1.2768 455 545 615 3280
Made-to-order item**
The above data are approximate and subject to normal manufacturing tolerances. Where required, the compatibility with glands, connectors and accessories should be verified
using actual dimensions of the product.
* Ampacity values shown above are per the National Electrical Code Table 310.15(B)(16) (formerly Table 310.16).
** For Made-to-order items: Minimum Runs, Pricing & Lead Times are subject to the plant’s production schedule.
PRINT LEGENDS QI Sizes:
STRANDED CONDUCTOR SIZES 8 – 1 AWG (IN ALL COLORS):
CME WIRE & CABLE QI® E102470 S (UL) MTW OR THHN OR THWN-2 OR AWM OR GR II SIZE AWG (SIZE mm²) CU 600 V VW-1 SR OR C(UL) TYPE T90 NYLON OR
TWN75 FT1.
CONDUCTOR SIZES 1/0 AWG – 1000 kcmil (IN ALL COLORS):
CME WIRE & CABLE QI® E102470 S (UL) MTW OR THHN OR THWN-2 OR AWM OR GR II SIZE AWG (SIZE mm²) CU 600 V VW-1 SR FOR CT USE OR C(UL) TYPE T90
NYLON OR TWN75 FT1.
PRINT LEGENDS: 14 – 10 AWG:
SOLID:
CME WIRE & CABLE E95989 S (UL) THHN OR THWN-2 OR AWM OR GR II (SIZE) AWG (SIZE mm²) CU 600 V VW-1 OR C(UL) TYPE T90 NYLON OR TWN75 FT1.
STRANDED:
CME WIRE & CABLE E102470 S (UL) MTW OR THHN OR THWN-2 OR AWM OR GR II (SIZE) AWG (SIZE mm²) CU 600 V VW-1 OR C(UL) TYPE T90 NYLON OR TWN75 FT1.