Manufactured for Long Life
Allied EMT is precision manufactured from high
grade mild strip steel for exceptional durability and
long-lasting life. Allied EMT is hot galvanized using
Allied’s patented in-line Flo-Coat
®
process.
This process combines zinc, a conversion coating, and
a clear organic polymer top-coat to form a triple layer of
protection against corrosion and abrasion.
EMI SHIELDING
Allied EMT greatly reduces electromagnetic fields,
effectively shielding computers and sensitive
electronic equipment from the electromagnetic
interference caused by power distribution systems.
FULL CODES & STANDARDS COMPLIANCE
Allied EMT is listed to Underwriters Laboratories Safety
Standard UL 797 and meets ANSI C80.3, which have
been adopted as federal specifications in lieu of WWC
563. EMT is recognized as an equipment grounding
conductor by NEC Section 250-118. Documentation for
compliance with NEC Article 250 is also available in the
GEMI (Grounding and Electro-Magnetic Interference)
analysis software and related research studies found at
the www.alliedeg.com website.
Installation of EMT shall be in accordance with the
National Electrical Code and the UL listing information.
Allied EMT is listed in category FJMX. Master bundles
conform to NEMA Standard RN2.
SPECIFICATION DATA
To specify Allied EMT, include the following: Electrical
Metallic Tubing shall be equal to that manufactured by
Allied Tube & Conduit Corporation. EMT shall be hot
galvanized steel O.D. with an organic corrosion
resistant I.D. coating and shall be produced in
accordance with U.L. Safety Standard #797 and
ANSI C80.3 and shall be listed by a nationally
recognized testing laboratory with follow-up service.
Where Kwik-Fit
®
EMT is used it shall also meet U.L.
Safety Standard #514-B. Note that these U.L. and
ANSI standards have been adopted by the federal
government and separate military specifications no
longer exist.
U.S. Metric lb. kg. in. mm in. mm ft. m
1/2 16 30 13.6 0.706 17.9 0.042 1.07 7000 2135.0
3/4 21 46 20.9 0.922 23.4 0.049 1.25 5000 1525.0
1 27 67 30.4 1.163 29.5 0.057 1.45 3000 915.0
1-1/4 35 101 45.8 1.510 38.4 0.065 1.65 2000 610.0
1-1/2 41 116 52.6 1.740 44.2 0.065 1.65 1500 457.5
2 53 148 67.1 2.197 55.8 0.065 1.65 1200 366.0
2-1/2 63 216 98.0 2.875 73.0 0.072 1.83 610 186.1
3 78 263 119.3 3.500 88.9 0.072 1.83 510 155.6
3-1/2 91 249 158.3 4.000 101.6 0.083 2.11 370 112.9
4 103 393 178.2 4.500 114.3 0.083 2.11 300 91.5
1
Outside diameter tolerances
:
+/- .005 in. (.13mm) for trade sizes 1/2 (16mm) through 2 (53mm);
+/- .010 in. (.25mm) for trade sizes 2-1/2 (63mm);
+/- .015 in. (.38mm) for trade size 3 (78mm);
+/- .020 in. (.51mm) for trade sizes 3-1/2 (91mm) and 4 (103mm).
NOTE: Length = 10 ft. (3.05m) with a tolerance of
+_
.25 in. (6.35 mm)
Weights and Dimensions for Electrical Metallic Tubing
U.S. Metric lb. kg. in. mm in. mm ft. m
2 53 148 67.1 2.197 55.8 0.065 1.65 500 152.4
2-1/2 63 216 98.0 2.875 73.0 0.072 1.83 350 106.8
3 78 263 119.3 3.500 88.9 0.072 1.83 300 91.5
3-1/2 91 349 158.3 4.000 101.6 0.083 2.11 250 76.3
4 103 393 178.2 4.500 114.3 0.083 2.11 250 76.3
Weights and Dimensions for Kwik-Fit EMT
1
Outside diameter tolerances
:
+/- .005 in. (.13mm) for trade size 2 (53mm);
+/- .010 in. (.25mm) for trade size 2-1/2 (63mm);
+/- .015 in. (.38mm) for trade size 3 (78mm);
+/- .020 in. (.51mm) for trade sizes 3-1/2 (91mm) and 4 (103mm).
NOTE: Length = 10 ft. (3.05m) with a tolerance of
+_
.25 in. (6.35 mm)
Trade Size
Designator
Approx. Wt. Per
100 Ft. (30.5M)
Nominal Outside
Diameter
1
Nominal
Wall
Thickness
Quantity In
Master Bundle
Quantity In
Master Bundle
Nominal
Wall
Thickness
Nominal Outside
Diameter
1
Approx. Wt. Per
100 Ft. (30.5M)
Trade Size
Designator