Cut Sheet
2
Cerro W
ire & Cable Co., Inc.
1099 Thompson Road, SE • Hartselle, AL 35640
Phone 256.773.2522 • Fax 256.773.5849 • www.cerrowire.com
Package Code K R M P
AWG Size 1000’ reel 2000’ reel 2500’ reel 5000’ reel
8 Stranded X X
6 Stranded X X
4 Stranded X X
3 Stranded X X
2 Stranded X X
1 Stranded X X
1/0 X X
2/0 X X
3/0 X X
4/0 X X
250 MCM X X
350 MCM X X
400 MCM X X
500 MCM X X
600 MCM X X
COPPER XHHW-2
(XLP) Insulated Copper Conductors
Polytherm Cross-Linked Polyethylene
• 90˚C Dry or Wet
• 600 Volts
• 1/0 and larger rated for CT use
• Sunlight Resistant
• Gasoline and Oil Resistant I & II
APPLICATIONS
• For use in conduit or other
recognized raceways for
service, feeder, and branch
circuit applications as specified
in the NEC
®
• Good choice for industrial
applications where better
insulation toughness and
resistance to moisture and
heat is desired
• For use in wet or dry locations
at temperatures up to 90˚C
• Sunlight resistant
CONDUCTORS
• Stranded conductors:
Uncoated, soft copper per
ASTM-B8 (2 AWG and 250 MCM
- 750 MCM), and ASTM-B787
(1 AWG - 4/0)
INSULATION
• XLP (cross-linked polyethylene)
INDUSTRY STANDARDS
• UL 44 - File No. E63539
• CSA LL 82214
•
AS
TM-B3
• ASTM-B8
• ASTM-B787
• Federal Specification A-A-59544
•
NFPA70: National Electrical Code
®
• NEMA WC70/ICEA S-95-658
SURFACE PRINT
•
Sample: 2 AW
G XH
HW-2 600V
SUN-RES GASOLINE & OIL
RESISTANT I & II (UL)
E63539/XLPE RW90
(-40˚C) CSA LL 82214