Cut Sheet

COPPER XHHW-2
90˚C Dry or Wet
600 Volts
1/0 and larger rated for CT use
Sunlight Resistant
Gasoline and Oil Resistant I & II
1
Cerro W
ire & Cable Co., Inc.
1099 Thompson Road, SE • Hartselle, AL 35640
Phone 256.773.2522 • Fax 256.773.5849 • www.cerrowire.com
(XLP) Insulated Copper Conductors
Polytherm Cross-Linked Polyethylene
P
roduct
Code
Number
C
onductors
I
nsulation
Thickness
Mils.
Approx. O.D.
Inches
A
llowable Ampacities*
A
pprox.
Net Wt.
lbs./m ft.
AWG
Size
No. of
Strands
60˚C
**
75˚C
***
90˚C
****
117-4000 8 7 45 0.240 40 50 55 65
117-4200 6 7 45 0.280 55 65 75 97
117-4400 4 7 45 0.330 70 85 95 148
1
17-4500
3 7 45 0.3
53
- - 1
10
1
80
117-4600 2 7 45 0.390 95 115 130 229
117-4700 1 19 55 0.450 110 130 150 293
117-5000 1/0 19 55 0.489 125 150 170 364
117-5200 2/0 19 55 0.530 145 175 195 449
117-5400 3/0 19 55 0.550 165 200 225 559
117-5600 4/0 19 55 0.640 195 230 260 698
117-6000 250 37 65 0.710 215 255 290 834
117-6400 300 37 65 0.760 - - 320 995
117-6800
350
37 65 0.820 260 310
350
1152
117-7200 400 37 65 0.860 280 335 380 1309
117-8000 500 37 65 0.950 320 380 430 1622
117-8400 600 61 80 1.040 355 420 475 1947
*
P
er Table 310-16 NEC
®
** For termination to equipment for circuits rated 100 amperes or less or marked for Nos.
1
4 through 1 conductors.
*** For termination to equipment for circuits rated over 100 amperes or marked for conductors
larger than No. 1.
**** Wet or dry locations.
APPLICATIONS
For use in conduit or other
recognized raceways for
service, feeder, and branch
circuit applications as specified
in the NEC
®
Good choice for industrial
applications where better
insulation toughness and
resistance to moisture and
heat is desired
For use in wet or dry locations
at temperatures up to 90˚C
Sunlight resistant
CONDUCTORS
Stranded conductors:
Uncoated, soft copper per
ASTM-B8 (2 AWG and 250 MCM
- 750 MCM), and ASTM-B787
(1 AWG - 4/0)
INSULATION
XLP (cross-linked polyethylene)
INDUSTRY STANDARDS
UL 44 - File No. E63539
CSA LL 82214
AS
TM-B3
ASTM-B8
ASTM-B787
Federal Specification A-A-59544
NFPA70: National Electrical Code
®
NEMA WC70/ICEA S-95-658
SURFACE PRINT
Sample: 2 AW
G XH
HW-2 600V
SUN-RES GASOLINE & OIL
RESISTANT I & II (UL)
E63539/XLPE RW90
(-40˚C) CSA LL 82214