Cut Sheet
Part Number
Size
(AWG)
Strand
(no.)
Insulation Thickness
(mils)
Grounding Conductor
(AWG)
PVC Jacket Thickness
(mils)
Approx. Diameter Overall
(in.)
Approx. Net Weight
(lb./1000')
Ampacity*
(30°C ambient) 90°C Wet/Dry
SER6/3G6 6 7 45 6 30 0.75 432 75
SER4/3G6 4 7 45 6 30 0.82 597 95
SER3/3G5 3 7 45 5 30 0.92 747 115
SER2/3G4 2 7 45 4 30 0.97 901 130
SER1/3G3 1 19 55 3 30 1.09 1,122 145
SER1/03G2 1/0 19 55 2 30 1.19 1,387 170
SER2/03G1 2/0 19 55 1 30 1.29 1,719 195
SER3/03G1/0 3/0 19 55 1/0 30 1.42 2,138 225
SER4/03G2/0 4/0 19 55 2/0 30 1.56 2,661 260
*Per NEC Table 310.15 (B)(16). NOTE: The data shown is approximate and subject to standard industry tolerances.
TRAY & POWER CABLE
SE-R
XHHW-2/PVC, Service Entrance
600 Volt Copper
Description:
3 conductors, stranded, insulated with heat and moisture resistant crosslinked
polyethylene (type XHHW-2) and phase identified. Cabled with bare copper
ground conductor. Cable core covered with flame retardant binder tape and
overall grey PVC jacket.
Standards:
UL 44 and UL 854
ICEA S-95-658/NEMA WC70
Temperature Rated at 90°C Wet/Dry
Sunlight Resistant
Color Code: K-1 Stripes
RoHS Compliant