Cut Sheet

January 13, 2015 ©2015 CME Wire and Cable, Inc. All Rights Reserved.
CME Wire and Cable | 495 Horizon Drive NE, Suite 100, Suwanee, Georgia 30024 | www.cmewire.com | 770.623.0001
Medium Voltage Cables - Single Conductor
A l u m i n u m
C o n d u C t o r
3
2
1
6
5
4
5 kV – 35 kV, Copper Tape Shielded
MV-105 EPR Insulated, PVC Jacketed
Features
UL listed as MV-105.
Rated as Sunlight Resistance
for CT use, 1/0 AWG and larger.
Jacket is rated as Oil Resistance I.
True Triple extrusion system and
closed handling raw materials
system, to eliminate any contact
with ambient, until extrusion
process ends.
Application
Primary power and distribution
circuits in industrial and
commercial installations,
power circuits in generating
plants where line to ground
fault current are within shield
capabilities.
May be used in wet or dry
locations, installed in cable
trays, raceways, duct, and
open air, aerially or directly
buried as permitted by NEC.
Standards
UL 1072
Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74
5 kV – 46 kV Shielded Power
Cables.
ICEA S-97-682
Standard for Utility Shielded
Power Cables Rated 5 kV – 46 kV.
AEIC CS8
Specification for Extruded
Dielectric, Shielded Power Cables
Rated 5 kV – 46 kV.
Specifications
Maximum operating voltage:
5 kV to 35 kV 100% and 133% IL
Maximum conductor operation
temperatures:
Wet and dry locations
Normal: 105 °C
Emergency: 140 °C
Short Circuit: 250 °C
Engineering
Information
1. Conductor: Soft annealed
uncoated copper compacted
Class B per ASTM B496 or hard
drawn Aluminum-1350 compacted
Class B per ASTM B400 or
annealed AA-8000 Aluminum
compacted Class B per ASTM B80.
On request, strand filled or
compressed strand or tinned
copper conductor.
Sizes: 8 AWG (6 AWG Aluminum)
up to 1000 kcmil.
On request, larger conductor
sizes available.
2. Conductor Shield: Semi
conducting cross-linked
polyethylene (XLPE).
3. Insulation: Thermoset ethylene
propylene rubber (EPR).
On request, Amorphous EPR.
4. Insulation Shield: Semi
conducting cross-linked
polyethylene (XLPE).
5. Metallic Shield: Soft annealed
uncoated copper tape, 5 mil thick,
25% minimum overlap.
Optional: Tinned copper tape.
6. Jacket: Black sunlight
resistance and flame retardant
polyvinyl chloride (PVC) jacket.
Configuration Options:
On request, Triplex or Paralleled
configurations.

Summary of content (4 pages)