Size
AWG
or
kcmil
Number
of
Strands
Conductor
Diameter
100% Insulation Level (175 mil) 133% Insulation Level (220 mil)
Nominal
Diameter
Over Insulation
Jacket
Thickness
Approximate
Outside
Diameter
Approximate
Net Weight
Nominal
Diameter
Over Insulation
Jacket
Thickness
Approximate
Outside
Diameter
Approximate
Net Weight
Copper Aluminum Copper Aluminum
in in mil in lb/kft in mil in lb/kft
2 7 0.27 0.66 80 0.92 593 451 0.75 80 1.01 675 532
1 19 0.30 0.69 80 0.95 666 486 0.78 80 1.04 749 569
1/0 19 0.34 0.73 80 0.99 757 530 0.82 80 1.08 843 616
2/0 19 0.38 0.77 80 1.03 868 582 0.86 80 1.12 957 671
3/0 19 0.42 0.82 80 1.07 1006 645 0.91 80 1.16 1099 738
4/0 19 0.48 0.87 80 1.12 1175 720 0.96 80 1.22 1272 817
250 37 0.52 0.92 80 1.18 1329 791 1.01 80 1.29 1456 918
300 37 0.57 0.97 80 1.23 1515 871 1.06 80 1.34 1647 1002
350 37 0.62 1.02 80 1.30 1726 973 1.11 80 1.39 1837 1083
400 37 0.66 1.06 80 1.34 1909 1049 1.15 80 1.43 2023 1163
500 37 0.74 1.14 80 1.42 2270 1195 1.23 80 1.51 2389 1314
600 61 0.81 1.23 80 1.51 2637 1346 1.32 80 1.60 2763 1472
750 61 0.91 1.32 80 1.60 3164 1551 1.41 110 1.76 3402 1789
1000 61 1.06 1.47 110 1.82 4145 1995 1.56 110 1.94 4347 2197
25 kV EPR Insulated
Size
AWG
or
kcmil
Number
of
Strands
Conductor
Diameter
100% Insulation Level (260 mil) 133% Insulation Level (320 mil)
Nominal
Diameter
Over Insulation
Jacket
Thickness
Approximate
Outside
Diameter
Approximate
Net Weight
Nominal
Diameter
Over Insulation
Jacket
Thickness
Approximate
Outside
Diameter
Approximate
Net Weight
Copper Aluminum Copper Aluminum
in in mil in lb/kft in mil in lb/kft
1 19 0.30 0.86 80 1.12 829 649 0.97 80 1.23 910 713
1/0 19 0.34 0.90 80 1.16 926 699 1.02 80 1.30 1086 859
2/0 19 0.38 0.94 80 1.20 1043 757 1.06 80 1.34 1208 922
3/0 19 0.42 0.99 80 1.25 1187 827 1.11 80 1.39 1358 997
4/0 19 0.48 1.04 80 1.32 1390 935 1.16 80 1.44 1541 1086
250 37 0.52 1.10 80 1.38 1553 1016 1.22 80 1.50 1709 1172
300 37 0.57 1.15 80 1.43 1748 1103 1.27 80 1.55 1909 1264
350 37 0.62 1.19 80 1.47 1940 1187 1.31 80 1.59 2106 1353
400 37 0.66 1.24 80 1.52 2129 1269 1.36 80 1.64 2300 1440
500 37 0.74 1.31 80 1.59 2501 1426 1.43 110 1.78 2786 1710
600 61 0.81 1.40 80 1.68 2881 1590 1.52 110 1.90 3229 1939
750 61 0.91 1.49 110 1.84 3531 1918 1.62 110 1.99 3787 2174
1000 61 1.06 1.65 110 2.02 4488 2338 1.77 110 2.14 4711 2561
Medium Voltage / MV-105 EPR Insulated, PVC Jacketed, 5 kV – 35 kV, Copper Tape Shielded
Technical Data continued
15 kV EPR Insulated
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities: Refer to beginning of section.