Cut Sheet

©2015 CME Wire and Cable, Inc. All Rights Reserved.January 13, 2015
CME Wire and Cable | 495 Horizon Drive NE, Suite 100, Suwanee, Georgia 30024 | www.cmewire.com | 770.623.0001
Technical Data
35 kV EPR Insulated
Medium Voltage / MV-105 EPR Insulated, PVC Jacketed, 5 kV – 35 kV, Copper Tape Shielded
Technical Data continued
Size
AWG
or
kcmil
Number
of
Strands
Conductor
Diameter
100% Insulation Level (345 mil) 133% Insulation Level (420 mil)
Nominal
Diameter
Over Insulation
Jacket
Thickness
Approximate
Outside
Diameter
Approximate
Net Weight
Nominal
Diameter
Over Insulation
Jacket
Thickness
Approximate
Outside
Diameter
Approximate
Net Weight
Copper Aluminum Copper Aluminum
in in mil in lb/kft in mil in lb/kft
1/0 19 0.34 1.08 80 1.36 1147 920 1.23 80 1.51 1341 1115
2/0 19 0.38 1.12 80 1.40 1270 984 1.27 80 1.55 1470 1184
3/0 19 0.42 1.16 80 1.44 1422 1061 1.32 80 1.60 1628 1267
4/0 19 0.48 1.21 80 1.49 1607 1153 1.37 80 1.65 1820 1365
250 37 0.52 1.27 80 1.55 1778 1241 1.42 110 1.76 2103 1565
300 37 0.57 1.32 80 1.60 1980 1335 1.47 110 1.81 2314 1669
350 37 0.62 1.37 80 1.65 2179 1426 1.52 110 1.86 2522 1769
400 37 0.66 1.41 110 1.75 2479 1619 1.56 110 1.94 2776 1916
500 37 0.74 1.49 110 1.83 2867 1791 1.64 110 2.01 3176 2100
600 61 0.81 1.57 110 1.95 3315 2025 1.73 110 2.10 3586 2296
750 61 0.91 1.67 110 2.04 3877 2264 1.82 110 2.19 4161 2548
1000 61 1.06 1.82 110 2.19 4808 2658 1.97 110 2.35 5110 2960
The above data are approximate and subject to normal manufacturing tolerances. Other sizes available upon request.
Ampacities: Refer to beginning of section.