Cut Sheet

Phone: 888-593-3355
www.generalcable.com
SPEC 6560
September, 2016
Aluminum Uniblend
®
PVC High Speed
EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded
25 kV and 35 kV, UL Type MV-105, 133%/100% Ins. Levels, 345 Mils
Product Construction:
Conductor:
• 1/0 AWG thru 1000 kcmil 1350 aluminum
compact Class B strand
Extruded Strand Shield (ESS):
• Extruded thermoset semi-conducting stress-
control layer over conductor
Insulation:
Lead-free Ethylene Propylene Rubber (EPR)
insulation, contrasting in color to the black
semi-conducting shield layers
Extruded Insulation Shield (EIS):
• Thermoset semi-conducting polymeric layer free
stripping from insulation
Metallic Shield:
• 5 mil annealed copper tape with an
overlap of 25%
Jacket:
Low-friction, lead-free, flame-retardant, moisture-
and sunlight-resistant Polyvinyl Chloride (PVC)
Options:
• STRANDFILL
®
- blocked conductor. Tested in
accordance with ICEA T-31-610
Applications:
Superior performance in petrochemical plants,
pulp and paper mills, sewage and water
treatment plants, environmental protection
systems, railroads, mines, utility power
generating stations, steel mills, textile plants and
other industrial three-phase applications
Applications (contd.):
• For use in wet or dry locations when installed in
accordance with NEC
• For use in aerial, conduit, open tray and
underground duct installations
• For use in direct burial if installed in a system with
a ground conductor that is in close proximity, and
conforms with NEC 250.4(A)(5)
Features:
• Rated at 105
˚
C
High Speed low friction technology for easy
cable pulling
• Excellent heat, moisture and sunlight resistance
Excellent flame resistance
Outstanding corona resistance
• Flexibility for easy handling
High dielectric strength
Low moisture absorption
• Electrical stability under stress
Low dielectric loss
• Chemical-resistant
• Meets cold bend test at -35
˚
C
• 105°C rating for continuous operation
140°C rating for emergency overload conditions
250°C rating for short circuit conditions
Compliances:
• National Electrical Code (NEC)
• UL 1072
• ICEA S-93-639/NEMA WC74
• ICEA S-97-682
• AEIC CS8
• UL listed as Type MV-105 for use in accordance
with NEC, UL File # E90501
• UL 1685 UL Flame Exposure Test
• IEEE 1202 (70,000 BTU/hr)/CSA FT4
• EPA 40 CFR, Part 261 for leachable lead content
per TCLP method
• OSHA Acceptable
• RoHS Compliant
Packaging:
• Material cut to length and shipped on
non-returnable wood reels. Lengths in excess of
10,000 lbs. are provided on returnable steel reels
that require a deposit
• Extra charges apply for cuts less than 1000 ft.,
lagging, pulling eyes, paralleling and triplexing
CATALOG
NUMBER
COND.
SIZE
(AWG/
kcmil)
NOMINAL
CONDUCTOR
DIAMETER
INSULATION
DIAMETER
INCHES
NOMINAL
JACKET
THICKNESS
NOMINAL CABLE
ALUMINUM WEIGHT
COPPER
WEIGHT
A
MPACITY
CONDUIT
SIZING (4)
(INCHES)
DIAMETER WEIGHT
CONDUIT IN
AIR (1)
UNDERGROUND
DUCT (2) TRAY (3)
INCHES MIN. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C 105˚C 90˚C 105˚C
25 kV
¥
& 35 kV
¥¥
, UL TYPE MV-105, 133%/100% INS. LEVEL, 345 MILS
17061.13 510 8*
1/0 0.34 1.020 1.120 0.080 2.03 1.31 33.27 863 1285 99 147 99 147 150 170 155 165 150 170 5
17061.135208*
2/0 0.38 1.060 1.160 0.080 2.03 1.35 34.29 925 1377 125 186 103 153 175 200 175 190 175 195 5
17061.135308*
3/0 0.43 1.105 1.205 0.080 2.03 1.40 35.56 1000 1488 158 235 107 159 200 225 200 215 205 225 5
17061.135408
4/0 0.48 1.160 1.260 0.080 2.03 1.45 36.83 1093 1626 199 296 112 167 230 260 230 245 235 260 5
17061.13 6008*
250 0.53 1.210 1.315 0.080 2.03 1.51 38.35 1174 1747 234 348 116 173 255 290 250 270 260 285 5
17061.136208
350 0.62 1.310 1.410 0.080 2.03 1.60 40.64 1356 2018 329 490 125 186 310 350 305 330 325 355 5
17061.136508
500 0.74 1.430 1.530 0.080 2.03 1.72 45.21 1707 2540 468 696 135 201 385 430 370 400 400 445 6
17061.137008
750 0.91 1.610 1.710 0.110 2.79 1.96 49.78 2120 3155 703 1046 151 225 485 540 455 490 515 575 6
17061.137508
1000 1.06 1.760 1.865 0.110 2.79 2.10 53.59 2500 3720 937 1394 162 241 565 640 525 565 620 690 8
Dimensions and weights are nominal. Subject to industry tolerances.
* Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery.
(1) Ampacities are in accordance with Table 310.60(C)(74) of the NEC for triplexed or three single conductor aluminum cables in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C
(221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F).
(2) Ampacities are in accordance with Table 310.60(C)(78) of the NEC for triplexed or three single conductor aluminum cables in underground ducts (three conductors per duct), based on a conductor
temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor,
and earth thermal resistance (rho) of 90.
(3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an ambient air temperature of 40˚C (104˚F)
the ampacities are based on 75% of the values per Table 310.60(C)(70), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not
exceed 70% of the values per Table 310.60(C)(70).
(4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered but should be checked for individual installations.
¥ 100% insulation level is available upon request.
¥¥ 133% insulation level is available upon request.
Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE”.
b) The NESC Lightning bolt symbol is on all Uniblend
®
constructions.

Summary of content (1 pages)