Cut Sheet
UF-B
• With 90˚C Insulation
• 600 Volts
1
Cerro W
ire & Cable Co., Inc.
1099 Thompson Road, SE • Hartselle, AL 35640
Phone 256.773.2522 • Fax 256.773.5849 • www.cerrowire.com
Cirtuf
®
Underground Feeder Cable
Product
Code
Number
w/Ground
Conductors Thickness Mils. With Ground
A
WG No.
Conds.
N
o. of
Strands
PVC/Nylon Jacket
Ground Wire
C
able Dim
Mils.
Approx.
Net Wt.
lbs./m ft.
Size Strand
138-1402 14-2 SOL 19 30 14 1 190 x 400 67
138-1602 12-2 SOL 19 30 12 1 190 x 450 96
1
38-1802
1
0-2
S
OL
2
4
3
0
1
0
1 2
40 x 520
1
39
138-4002 8-2 7 35 45 10 1 220 x 690 223
138-4202 6-2 7 35 45 10 1 390 x 695 304
138-1403 14-3 SOL 19 30 14 1 215 x 615 104
138-1603 12-3 SOL 19 30 12 1 260 x 700 150
138-1803 10-3 SOL 24 30 10 1 250 x 750 212
138-4003 8-3 7 35 45 10 1 350 x 975 340
138-4203 6-3 7 35 45 10 1 400 x 1090 485
APPLICATIONS
• For use underground as a feeder
or branch-circuit cable where
p
rovided with overcurrent
protection of the rated ampacity
as specified by the NEC
®
. Direct
burial in the earth is permitted
• May be installed as interior
wiring in wet, dry, or corrosive
locations as specified by the NEC
®
• May be installed as nonmetallic-
sheathed cable as specified in
NEC
®
Section 340.10 (4)
• May be installed in locations
with temperatures up to 90˚C
but with the ampacity limited
to that of 60˚C conductors.
CONDUCTORS
• Solid conductors: Soft, uncoated
copper per ASTM-B3
• Stranded conductors: Uncoated
copper per ASTM-B3 and ASTM-B8
CONDUCTOR INSULATION
AND JACKET
• Color coded PVC (polyvinyl
chloride), rated 90˚C dry
• Insulated conductors also jacketed
with clear nylon (polyamide)
GROUNDING CONDUCTOR
•
Soft, uncoated copper per
ASTM-B3
ASSEMBLY
•
Insulated conductors are laid
parallel with (or without)
a bare grounding conductor
J
A
CKE
T
• A gray, sunlight resistant PVC
(polyvinyl chloride) is applied
directly over and around the
insulated and bare conductors