PARTS AND OPERATION MANUAL OPERATION AND PARTS MANUAL ULTRA-SILENTTM SERIES MODEL DCA-125USJ 50 Hz GENERATOR PARTS LIST NO. M3870400004 Revision #0 (03/11/05) THIS MANUAL MUST ACCOMPANY THE EQUIPMENT AT ALL TIMES.
PAGE 2 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
HERE'S HOW TO GET HELP PLEASE HAVE THE MODEL AND SERIAL NUMBER ON-HAND WHEN CALLING MQ POWER CORPORATE OFFICE 18910 Wilmington Ave. 800-421-1244 Carson, CA 90746 FAX: 310-632-2656 Email: mqpower@multiquip.com Internet: www.mqpower.com PARTS DEPARTMENT 800-427-1244 FAX: 800-672-7877 310-537-3700 FAX: 310-637-3284 SERVICE DEPARTMENT 800-835-2551 FAX: 310-638-8046 310-537-3700 TECHNICAL ASSISTANCE 800-478-1244 FAX: 310-631-5032 WARRANTY DEPARTMENT 800-835-2551, EXT. 279 FAX: 310-638-8046 310-537-3700, EXT.
TABLE OF CONTENTS MQ POWER DCA12USJ AC GENERA TOR GENERATOR California Proposition 65 Warning ..................................... 2 Here's How To Get Help .................................................... 3 Table Of Contents ............................................................. 4 Parts Ordering Procedures ............................................... 5 Specifications ................................................................... 6 Dimensions (Top, Side, Front) ...........................
PARTS ORDERING PROCEDURES When ordering parts, please supply the following information: ❒ ❒ ❒ ❒ ❒ ❒ ❒ Dealer account number Dealer name and address Shipping address (if different than billing address) Return fax number Applicable model number Quantity, part number and description of each part Specify preferred method of shipment: ✓ FedEx or UPS Ground Note: Unless otherwise indicated by customer, all ✓ FedEx or UPS Second Day or Third Day orders are treated as “Standard Orders”, and will ✓ FedEx or UPS Nex
DCA-125USJ (50 HZ)— SPECIFICATIONS Table 1. Generator Specifications Model DCA125USJ Type Revolving field, self ventilated, open protected type synchronous generator Armature Connection Star with Neutral Zig Zag Phase 3 Single Standby Output 110 KVA (88 KW) 63 KW Prime Output 100 KVA (80 KW) 58 KW Voltage 200V or 400V 200/100V Frequency 50 Hz Speed 1500 r pm Power Factor 0.8 1 Aux. AC Power Single Phase, 50 Hz Voltage 100 V Output 4.8 KW (2.4 KW x 2) Table 2.
DCA-125USJ (50 HZ)— DIMENSIONS (TOP, SIDE AND FRONT) Figure 1. Dimensions 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ) — SAFETY MESSAGE ALERT SYMBOLS FOR YOUR SAFETY AND THE SAFETY OF OTHERS! Safety precautions should be followed at all times when operating this equipment. Failure to read and understand the Safety Messages and Operating Instructions could result in injury to yourself and others. NOTE This Owner's Manual has been developed to provide complete instructions for the safe and efficient operation of the MQ Power Model DCA-125USJ (50 HZ)ULTRA-SILENT™ GENERATOR.
DCA-125USJ (50 HZ) — SAFETY MESSAGE ALERT SYMBOLS Accidental Starting ALWAYS place the engine ON/OFF switch in the OFF position, when the trowel is not in use. Over Speed Conditions NEVER tamper with the factory settings of the engine governor or settings. Personal injury and damage to the engine or equipment can result if operating in speed ranges above maximum allowable. Respiratory Hazard ALWAYS wear approved respiratory protection.
DCA-125USJ (50 HZ) — RULES FOR SAFE OPERATION CAUTION CAUTION: Failure to follow instructions in this manual may lead to serious injury or even death! This equipment is to be operated by trained and qualified personnel only! This equipment is for industrial use only. The following safety guidelines should always be used when operating the DCA-125USJ (50 HZ)Generator: GENERAL SAFETY ■ DO NOT operate or service this equipment before reading this entire manual.
DCA-125USJ (50 HZ) — RULES FOR SAFE OPERATION ■ ALWAYS make sure that electrical circuits are properly grounded per the National Electrical Code (NEC) and local codes before operating generator. Severe injury or death! by electrocution can result from operating an ungrounded generator. ■ ALWAYS be sure the operator is familiar with proper safety precautions and operations techniques before using generator. ■ ALWAYS store equipment properly when it is not being used.
DCA-125USJ (50 HZ)— RULES FOR SAFE OPERATION Battery The battery contains acids that can cause injury to the eyes ■ ALWAYS service air cleaner frequently to prevent engine and skin. To avoid eye irritation, always wear safety glasses. Use well insulated gloves when picking up the battery. Use malfunction. the following guidelines when handling the battery: ■ ALWAYS disconnect the negative battery terminal before performing service on the generator. ■ NEVER run engine without air filter.
DCA-125USJ (50 HZ)— RULES FOR SAFE OPERATION Towing Safety Precautions ■ Avoid sharp turns. CAUTION: ■ Trailer should be adjusted to a level position at all times when towing. Conform to Department of Transportation ■ Raise and lock trailer wheel stand in up position when transporting. (DOT) Safety Towing Regulations before towing generator. ■ DOT Requirements include the following: z Connect and test electric brake operation.
DCA-125USJ (50 HZ)— INSTALLATION Figure 2. Typical Generator Grounding Application PAGE 14 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— INSTALLATION Outdoor Installation Install the generator in a area that is free of debris, bystanders, and overhead obstructions. Make sure the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes. The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture.
DCA-125USJ (50 HZ)— TOWING SAFETY PRECAUTIONS Towing Safety Precautions CAUTION CAUTION: Check with your local county or state safety towing regulations before towing your generator. To reduce the possibility of an accident while transporting the generator on public roads, always make sure the trailer (Figure 4) that supports the generator and the towing vehicle are in good operating condition and both units are mechanically sound.
DCA-125USJ (50 HZ)— TRAILER SPECIFICATIONS 5. Frame Width - Measurement is from fender to fender ALWAYS make sure the trailer is in good 6. Jack Stand - Trailer support device with maximum pound requirement from the tongue of the trailer. operating condition. Check the tires for proper inflation and wear. Also check the 7. Coupler - Type of hitch used on the trailer for towing. wheel lug nuts for proper tightness. 8. Tire Size - Indicates the diameter of the tire in inches (10,12,14, etc.
DCA-125USJ (50 HZ)— GENERATOR DECALS The DCA-125USJ (50 HZ)generator is equipped with a number of safety decals (Figure 4). These decals are provided for operator safety and maintenance information. The illustration below and on the preceding page show the decals as they appear on the machine. Should any of these decals become unreadable, replacements can be obtained from your dealer. Figure 4. Generator Decals PAGE 18 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— GENERATOR DECALS Figure 4. Generator Decals (Cont.) 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— GENERAL INFORMATION DCA-125USJ (50 HZ) Series Familiarization Generator The MQ Power Model DCA-125USJ (50 HZ)is a 80 kW generator (Figure 5) that is designed as a high quality portable (requires a trailer for transport) power source for telecom sites, lighting facilities, power tools, submersible pumps and other industrial and construction machinery.
DCA-125USJ (50 HZ)— MAJOR COMPONENTS Table 3. Generator Major Components ITEM NO. DESCRIPTION 1 Muffler Assembly 2 Engine Assembly 3 Enclosure Assembly 4 Generator Assembly 5 Output Terminal Assembly 6 Fuel Tank Assembly 7 Battery Assembly 8 Generator Control Panel Assembly 9 Engine Operating Panel Assembly Figure 5. Major Components 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
NOTE PAGE PAGE 22 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— GENERATOR CONTROL PANEL Figure 6. Generator Control Panel The definitions below describe the controls and functions of Located behind the generator control panel is the Generator the DCA-125USJ (50 HZ)Generator Control Panel (Figure Control Box. This box contains some of the necessary electronic components required to make the generator 6). 1. Main Circuit Breaker – This three-pole, 300A main function. 2.
DCA-125USJ (50 HZ)— ENGINE OPERATING PANEL Figure 7. Engine Operating Panel PAGE 24 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENGINE OPERATING PANEL The definitions below describe the controls and functions of During cranking cycle , The MPEC will attempt to crank the the DCA-125USJ (50 HZ)Engine Operating Panel (Figure engine for 10 seconds before disengaging. If the engine does 7). 1. Panel Light – Normally used in dark areas or at night not engage (start) by the third attempt, the engine will be time. When activated, panel lights will illuminate.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL FAMILIARIZATION Output Terminal Panel The Output Terminal Panel (Figure 8) shown below is located on the right-hand side (left from control panel) of the generator. Lift up on the cover to gain access to receptacles and terminal lugs. NOTE Terminal legs “O” and “Ground” are considered bonded grounds.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL FAMILIARIZATION 100 VAC GFCI Receptacles There are two 100 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any voltage selector switch position. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the UVWO terminals.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL FAMILIARIZATION Connecting Loads Loads can be connected to the generator by the Ouput Terminal Lugs or the convienience receptacles. (See Figure 13). Make sure to read the operation manual before attempting to connect a load to the generator. To protect the output terminals from overload, a 3-pole, 300A main circuit breaker is provided. Make sure to switch ALL circuit breakers to the OFF position prior to starting the engine.
DCA-125USJ (50 HZ)— LOAD APPLICATION Single Phase Load Three Phase Load Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment. When calculating the power requirements for 3-phase power use the following equation: Generally, the wattage listed on the nameplate of the equipment is its rated output.
DCA-125USJ (50 HZ)— GENERATOR OUTPUTS Voltage Selector Switch The voltage selector switch (Figure 16) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection. Generator Output Voltages A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by using the voltage selector switch (Figure 15).
DCA-125USJ (50 HZ)— GAUGE READING How to Read the Output Terminal Gauges. The gauges and selector switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied at the Output terminals lugs. Before taking a reading off either gauge, set the Voltage Selector Switch (Figure 17) to the position which produces the required voltage (For example, for 3Ø 200V, choose the center 3Ø 240/ 139V position on the voltage selector switch.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL CONNECTIONS UVWO Terminal Output Voltages Various output voltages can be obtained using the Output Terminal Lugs.. The voltages at the terminals are dependent on the position of the Voltage Selector Switch and the adjustment of the Voltage Regulator Control Knob. Remember the voltage selector switch determines the range of the output voltage. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL PANEL CONNECTIONS 3Ø 440/254 Output Terminal Lug Voltages 1Ø 200V/100V Output Terminal Lug Voltages 1. Place the voltage selector switch in the 3Ø 480/277 1. Place the voltage selector switch in the 1Ø 240/120 position as shown in Figure 27. position as shown in Figure 29. Figure 27. Voltage Selector Switch 480/277V Three-Phase Position Figure 29. Voltage Selector Switch 240/120V Single-Phase Position 2. Connect the load wires to the Output Terminal Lugs as 2.
DCA-125USJ (50 HZ)— PRE-SETUP Circuit Breakers Fuel Check To protect the generator from an overload, a 3-pole, 300 amp, main circuit breaker is provided to protect the U,V, and W Output Terminals from overload. In addition two single-pole, 20 amp GFCI circuit breakers are provided to protect the GFCI receptacles from overload. Three 50 amp load circuit breakers have also been provided to protect the auxiliary receptacles from overload.
DCA-125USJ (50 HZ)— PRE-SETUP Refueling Procedure: 3. DANGER: Open cabinet doors on the “right side” of the generator (from generator control panel position). Remove fuel cap and fill tank (Figure 34). Diesel fuel and its vapors are dangerous to your health and the surrounding environment. Avoid skin contact and/or inhaling fumes. 1. Level Tanks – make sure fuel cells are level with the ground. Failure to do so will cause fuel to spill from the tank before reaching full capacity (Figure 33).
DCA-125USJ (50 HZ)— PRE-SETUP Coolant (John Deere Antifreeze/Summer Coolant/Water) John Deere recommends John Deere Antifreeze/Summer Coolant for use in thier engines, which can be purchased in concentrate (and mixed with 50% demineralized water) or pre-diluted. See the John Deere Engine Owner's Manual for further details. NOTE When the antifreeze is mixed with water, the antifreeze mixing ratio must be less than 50%.
DCA-125USJ (50 HZ)— PRE-SETUP Battery When connecting battery do the following: This unit is of negative ground DO NOT connect in reverse. 1. NEVER connect the battery cables to the battery Always maintain battery fluid level between the specified terminals when the MPEC Control Switch is in either marks. Battery life will be shortened, if the fluid level are not the MANUAL position. ALWAYS make sure that the MPEC Control Switch is in the OFF/RESET position properly maintained.
DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (MANUAL) WARNING: 4. Close all engine enclosure doors (Figure 40). The engine's exhaust contains harmful emissions. ALWAYS have adequate ventilation when operating. Direct exhaust away from nearby personnel. Before Starting CAUTION: Figure 40. Engine Enclosure Doors NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position. 5.
DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (MANUAL) Starting (Manual) 9. The generator's frequency meter (Figure 45) should be displaying the 60 cycle output frequency in HERTZ. 8. Place the MPEC Control Switch in the MANUAL position to start the engine (Figure 42). Figure 45. Frequency Meter (Hz) 10. The generator's AC-voltmeter (Figure 46) will display the generator’s output in VOLTS.
DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (MANUAL) 12. The engine oil pressure gauge (Figure 49) will indicate the oil pressure (kg/ cm2) of the engine. Under normal operating conditions the oil pressure is approximately 35~65 PSI. 15. Place the main, GFCI, and aux. circuit breakers in the ON position (Figure 52). Figure 49. Oil Pressure Gauge 13. The coolant temperature gauge (Figure 50) will indicate the coolant temperature.
DCA-125USJ (50 HZ)— GENERATOR START-UP PROCEDURE (AUTO MODE) DANGER: Starting (Auto Mode) Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch. 2. Place the MPEC Control Switch (Figure 54) in the AUTO position . Figure 54. MPEC Control Switch (AUTO) CAUTION: When connecting the generator to a 3.
DCA-125USJ (50 HZ)— GENERATOR SHUT-DOWN PROCEDURE Emergency Shutdown Procedure NEVER stop the engine suddenly except 1. To shut-down the engine in the event of an emergency, switch the MAIN, GFCI and LOAD (Figure 39) circuit in an emergency. DO NOT use the breakers to OFF position. emergency stop switch a as method of shutting down the generator. This switch is 2. Place the MPEC Control Switch switch (Figure 55) to ONLY to be used in the event of an the OFF/RESET position. emergency.
DCA-125USJ (50 HZ)— MAINTENANCE 10 Hrs DAILY TABLE 11.
DCA-125USJ (50 HZ)— MAINTENANCE Air Removal Flushing Out Radiator and Replacing Coolant If air enters the fuel injection system of a diesel engine, z Open both cocks located at the crankcase side and at starting becomes impossible. After running out of fuel, or the lower part of the radiator and drain coolant. Open the after disassembling the fuel system, bleed the system radiator cap while draining. Remove the overflow tank according to the following procedure. See the John Deere and drain.
NOTE PAGE 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— TRAILER BRAKES MAINTENANCE Brakes Trailer brakes should be inspected the first 200 miles of operation. This will allow the brake shoes and drums to seat properly. After the first 200 mile interval, inspect the brakes every 3,000 miles. If driving over rough terrain, inspect the brakes more frequently. Figure 56 displays the major hydraulic surge brake components that will require inspection and maintenance.
DCA-125USJ (50 HZ)— TRAILER MAINTENANCE Tires/Wheels/Lug Nuts Tires and wheels are a very important and critical components of the trailer. When specifying or replacing the trailer wheels it is important the wheels, tires, and axle are properly matched. CAUTION: Suspension The leaf suspension springs and associated components (Figure 57) should be visually inspected every 6,000 miles for signs of excessive wear, elongation of bolt holes, and loosening of fasteners.
DCA-125USJ (50 HZ)— TRAILER MAINTENANCE Lug Nut Torque Requirements It is extremely important to apply and maintain proper wheel mounting torque on the trailer. Be sure to use only the fasteners matched to the cone angle of the wheel. Proper procedure for attachment of the wheels is as follows: 1. Start all wheel lug nuts by hand. 2. Torque all lug nuts in sequence (see Figure 58). DO NOT torque the wheel lug nuts all the way down. Tighten each lug nut in 3 separate passes as defined by Table 15. 3.
DCA-125USJ (50 HZ)— TRAILER WIRING DIAGRAM Figure 59. Trailer/Towing Vehicle Wiring Diagram 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— GENERATOR WIRING DIAGRAM Figure 60. Generator Wiring Diagram PAGE 50 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENGINE WIRING DIAGRAM Figure 61. Engine Wiring Diagram 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— TROUBLESHOOTING (GENERATOR) Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, use Table 16 shown below for diagnosis of the Generator. If the problem cannot be remedied, consult our company's business office or service plant. TABLE 16.
DCA-125USJ (50 HZ)— TROUBLESHOOTING (ENGINE CONTROLLER) Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, use Table 17 (Engine Controller Troubleshooting) as a basic guideline for troubleshooting the Microprocessor Engine Controller unit (MPEC). If the problem cannot be remedied, consult our company's business office or service plant. TABLE 17. ENGINE CONTROLLER TROUBLESHOOTING Sympton Low oil pressure light is on.
EXPLANATION OF CODE IN REMARKS COLUMN How to read the marks and remarks used in this parts book. Items Found In the “Remarks” Column Serial Numbers-Where indicated, this indicates a serial number range (inclusive) where a particular part is used. Model Number-Where indicated, this shows that the corresponding part is utilized only with this specific model number or model number variant.
DCA-125USJ (50 HZ)— SUGGESTED SPARE PARTS DCA-125USJ (50 HZ)W/JOHN DEERE 4045TF275 DIESEL ENGINE 1 TO 3 UNITS Qty. P/N Description 5 .............. 0602041292 ........................ FILTER, OIL 5 .............. 0602042594 ........................ FILTER, FUEL, PRIMARY 5 .............. 0602042595 ........................ FILTER, FUEL, FINAL 3 .............. 0602046377 ........................ ELEMENT, AIR 1 .............. 0602011493 ........................ BELT, FAN 1 .............. 0605505070 ........
DCA-125USJ (50 HZ)— GENERATOR ASSY. GENERATOR ASSY. PAGE 56 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— GENERATOR ASSY. GENERATOR ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— CONTROL BOX ASSY. CONTROL BOX ASSY. PAGE 58 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— CONTROL BOX ASSY. CONTROL BOX ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— CONTROL BOX ASSY. CONTROL BOX ASSY. PAGE 60 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— CONTROL BOX ASSY. CONTROL BOX ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— ENGINE AND RADIATOR ASSY. ENGINE AND RADIATOR ASSY. PAGE 62 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENGINE AND RADIATOR ASSY. ENGINE AND RADIATOR ASSY. NO. PART NO. PART NAME QTY. REMARKS 1 M3923200054 ENGINE & RADIATOR SET ................................. 1 ........ JOHN DEERE 6068TF275 1-1 0602041292 CARTRIDGE, OIL FILTER .................................... 1 ........ RE504836 1-2 0602042594 CARTRIDGE, PRIMARY, FUEL FILTER ............... 1 ........ RE517181 1-3 0602042595 CARTRIDGE, FINAL, FUEL FILTER .................... 1 ........ RE509031 1-4 0602011493 FAN BELT ...............
DCA-125USJ (50 HZ)— ENGINE AND RADIATOR ASSY. ENGINE & RADIATOR ASSY. PAGE 64 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENGINE AND RADIATOR ASSY. ENGINE & RADIATOR ASSY. NO. PART NO. 31 0605515197 32 0602022563 33 0602022561 34 0603306590 35 0603300285 36 0605511395 37 0603306395 38 0602021070 39 0269200450 40 M9300000203 41 0602010900 42 M3316100303 43 0016908020 44 0199102200 45 0193600700 46 0193601000 47 0605515106 48 M3326000204 49 0605515149 50 M3260600104 52 0602202592 53 0027106016 54 0030006000 55 0017112025 56 0040512000 57 0602123261 58 1718939010 PART NAME QTY.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL ASSY. OUTPUT TERMINAL ASSY. PAGE 66 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— OUTPUT TERMINAL ASSY. OUTPUT TERMINAL ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— BATTERY ASSY. BATTERY ASSY. PAGE 68 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— BATTERY ASSY. BATTERY ASSY. NO. PART NO. 1 0602220196 2 M9310500404 3 M9103000504 4 0602220921 5 M3346900904 6 M3346901004 7 8 0030012000 8A 0040012000 9 0017112025 9A 0040512000 10 0040520000 PART NAME QTY. REMARKS BATTERY ....................................................... 1 ............. 4D-2 BATTERY SHEET 1 BATTERY BAND 1 BATTERY BOLT SET 2 BATTERY CABLE 1 BATTERY CABLE 1 CABLE ........................................................... 1 .............
DCA-125USJ (50 HZ)— MUFFLER ASSY. MUFFLER ASSY. PAGE 70 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— MUFFLER ASSY. MUFFLER ASSY. NO. PART NO. 1 M3330100402 2 0017112030 3 M3333000903 4 M3333200304 5 0017110040 6 M3333200204 7 0017108040 7 0017110035 8 M3333000803 9 0016908055 9 0017110050 10 0602325066 PART NAME QTY. REMARKS MUFFLER 1 HEX, HEAD BOLT 4 EXHAUST PIPE 1 GASKET 1 HEX, HEAD BOLT 4 GASKET 1 HEX, HEAD BOLT 4 HEX, HEAD BOLT ............................................. 4 ........... S/N 8500015~ EXHAUST PIPE 1 HEX, HEAD BOLT 4 HEX, HEAD BOLT ....................................
DCA-125USJ (50 HZ)— FUEL TANK ASSY. FUEL TANK ASSY. PAGE 72 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— FUEL TANK ASSY. FUEL TANK ASSY. NO. PART NO. 1 M3363001402 1A 0605505070 1B 0605501074 1C 0605516090 2 M3363001504 2A 0605505070 3 0191700260 4 0605515149 5 M3363200404 6 M9310500104 7 0016908020 8 0016908055 8A 0030008000 8B 0207308000 8C 0041208000 9 0191302500 10 0605515109 11 0191301200 12 0191301200 13 0605515109 14 0602042601 15 0222101000 PART NAME QTY.
DCA-125USJ (50 HZ)— ENCLOSURE #1 ASSY. ENCLOSURE #1 ASSY. ADD THE FOLLOWING DIGITS AFTER THE PART NUMBER WHEN ORDERING ANY PAINTED PANEL TO INDICATE COLOR OF UNIT: 1-ORANGE 2-WHITE 3-SPECTRUM GREY 4-SUNBELT GREEN 5-BLACK 6-CATERPILLAR YELLOW 7-CATO GOLD 8-RED THE SERIAL NUMBER MAY BE REQUIRED. PAGE 74 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENCLOSURE #1 ASSY. ENCLOSURE #1 ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— ENCLOSURE #1 ASSY. ENCLOSURE #1 ASSY. ADD THE FOLLOWING DIGITS AFTER THE PART NUMBER WHEN ORDERING ANY PAINTED PANEL TO INDICATE COLOR OF UNIT: 1-ORANGE 2-WHITE 3-SPECTRUM GREY 4-SUNBELT GREEN 5-BLACK 6-CATERPILLAR YELLOW 7-CATO GOLD 8-RED THE SERIAL NUMBER MAY BE REQUIRED. PAGE 76 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENCLOSURE #1 ASSY. ENCLOSURE #1 ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— ENCLOSURE #2 ASSY. ENCLOSURE #2 ASSY. ADD THE FOLLOWING DIGITS AFTER THE PART NUMBER WHEN ORDERING ANY PAINTED PANEL TO INDICATE COLOR OF UNIT: 1-ORANGE 2-WHITE 3-SPECTRUM GREY 4-SUNBELT GREEN 5-BLACK 6-CATERPILLAR YELLOW 7-CATO GOLD 8-RED THE SERIAL NUMBER MAY BE REQUIRED. PAGE 78 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— ENCLOSURE #2 ASSY. ENCLOSURE #2 ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— RUBBER SEALS ASSY. RUBBER SEALS ASSY. PAGE 80 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— RUBBER SEALS ASSY. RUBBER SEALS ASSY. NO. PART NO.
DCA-125USJ (50 HZ)— NAMEPLATE AND DECALS ASSY. NAMEPLATE AND DECALS ASSY. PAGE 82 — DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
DCA-125USJ (50 HZ)— NAMEPLATE AND DECALS ASSY. NAMEPLATE AND DECALS ASSY. NO. PART NO. PART NAME QTY. REMARKS 1 M1550000204 DECAL, NOTE ................................................... 1 ........... M15000020 2 M1550000703 DECAL, AUXILARY OUTPUT ............................ 1 ........... M15000070 3 M3550000004 DECAL, NOTE ................................................... 1 ........... M35000000 4 M3550001603 DECAL, GENERATOR CONTROL ..................... 1 ...........
Effective: October 1, 2002 PAYMENT TERMS TERMS AND CONDITIONS OF SALE — PARTS 5. Parts must be in new and resalable condition, in the original Multiquip package (if any), and with Multiquip part numbers clearly marked. 6. The following items are not returnable: Terms of payment for parts are net 10 days. FREIGHT POLICY All parts orders will be shipped collect or prepaid with the charges added to the invoice. All shipments are F.O.B. point of origin.
NOTE PAGE 1 DCA-125USJ (50 HZ) — OPERATION AND PARTS MANUAL — REV.
PARTS AND OPERATION MANUAL OPERATION AND PARTS MANUAL HERE'S HOW TO GET HELP PLEASE HAVE THE MODEL AND SERIAL NUMBER ON-HAND WHEN CALLING MQ POWER CORPORATE OFFICE 18910 Wilmington Ave. 800-421-1244 FAX: 310-632-2656 Carson, CA 90746 Email: mqpower@multiquip.com Internet: www.mqpower.