Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 39 to the OFF position.
3. Let the engine cool by running it for 3-5 minutes with no
load applied.
4. Place the
MPEC Control Switch
(Figure 55) to the
OFF/RESET position.
Figure 55. MPEC Control Switch (Off/Reset)
5. Verify that the
all
status LED on the MPEC display
are OFF (not lit).
6. Remove all loads from the generator.
DCA-150USJ — GENERATOR SHUT-DOWN PROCEDURE
Emergency Shutdown Procedure
1. To shut-down the engine in the event of an emergency,
switch the
MAIN
,
GFCI
and
LOAD
(Figure 39) circuit
breakers to OFF position.
2. Place the
MPEC Control Switch
switch (Figure 55) to
the OFF/RESET position.
NEVER stop the engine suddenly except in an emergency.
DO NOT use the emergency stop switch a as method of
shutting down the generator. This switch is ONLY to be
used in the event of an emergency.
WARNING -
SHUTTING DOWN THE GENERATOR