Operating instructions
NOTE: Installation that incorporate Standing Iron Radiation and systems manual vents high points. Follow the above
procedure than slatting with nearest manual air vent, open vent until water flows out; close vent. Repeat procedure, working
your way toward furthest air vent. It may be necessary to install basket strainer in older hydronic system where larger
amounts of sediment may be present. Annual cleaning of the strainer may be necessary.
SUGGESTED HYDRON1C PIPING FOR MUNCHK1N BOILER
FIGURE 7A
SYSTEM_ --__um
{_PURGE & BALANCE VALVE S_LY_
SYSTEM
EMERGCNCy
_ _ PUMP R--N G_S 9URN[_
_ I_BACK FLOW pREVENTER _ _ SV[TCH
:_ _)LOW PRESSURE FEED (15 LB NOMINAL)
_ _ EXPANSION TANK C0kD_ IN
_ _AIR VENT (Mir co bubbler Air EXHAUST_
El iminator RecoHended) pipe OdTL£T
• _ FLOW CHECK PORt
• _ I_RAIN V&LVE
_ yEMPERATURE & PRESSURE GAGE
_I_"UNION CDNNECT TD BDILER SUPPLY HOT CEINNEOT TO BDILER RETURN CQLD BACK
• ITERS SUPPLIED BY CONTRACTOR
_IILER
0 0 s_
_C]LER HOT
RETURN
COLD
ALL PIPES _ST I_ PR_Ly SLPpDR?Eg
_h_KIN BfllLER
_LL PIPC$ _Sl K p_RLV SUpt'flRTE_
F_,DNT
NOTE: BOILER CONNECTIONS
ARE 1 I/4"NPT
FIGURE 7B
F
C
T
t
O
N
21.
20.
19 ,
18"
17"
16,
15,
14
13'
12"
11
10"
9
8'
7
6
5
4
3
2
1
1 2 3 4 5 6 7 B g 10 11 12 13 14 15 16 17 18 1920 21 22 23
FLOW IN GALLONS PER MINUTE
TACOpRd GRUNOFOSp,_I
MUNCHKIN 80M 00"/'(_) 15-42.F 8po-2
MUNCHKIN 140M _ 0010V) 26"64F
MUNCHKIN 199M _ 0011(1) 26-116F
1) THE RECOMMENDED CIRCULATORS ARE BASED ON 1 GPM PER 10,000 BTU/HR W/20° At
PART 6
BOILER START UP
6-A. COMMON VENT TEST
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to
the common venting system placed in operation, while the other appliances remaining connected to the common venting
system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as the practical, close all building doors and windows and all doors between the space in which the appliances
remaining connected to the common venting system are located and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace
dampers.