3-A. GAS CONNECTION
Gas supply shall have a maximum inlet pressure of less than 14"water column
(350 ram), ½ pound pressure (3.4 kPa), and a minimum ofT' water column.
The entire piping system, gas meter, and regulator must be sized properly to
prevent pressure drop greater than 0.5" as stated in the National Fuel Gas Code.
This information is listed on the rating plate. It is very important that yon are
connected to the type of gas as noted on the rating plate. "LP" for liquefied
_RVlCE S_ll_ CCr V_-VE
Mt_T lie _1
LUST _/_' Lp_
_Ep t_
petroleum, or propane gas; or "Nat" natural gas or city gas. All gas connections must
be approved by the local gas supplier, or utility in addition to the governing authority, prior to turning the gas supply on. The
nipple provided is ½", and it is mandatory that a %" to ½" reducing bushing (provided) is used, threaded into the branch of a
%" tee, and a drip leg fabricated, as per the National Fuel Gas code. You must ensure that the entire gas line to the
connection at the Munchkin is no smaller than 3/4". Once all the inspections have been performed, the piping must be leak
tested. Iftbe leak test requirement is a higher test pressure than the maximum inlet pressure, you must isolate the Munchkin
from the gas line. In order to do this, you must shut the gas off following lighting instruction on page 11. Unscrew the
threaded mounting flange which is located on the gas valve which will prevent high pressure which may damage the gas
valve. In the event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be
replaced. Never use an onen flame (lit match, li_hterI to check _as connections.
3-B. GAS PIPING
1.
2.
WARNING
Failure to follow all nrecautions could result in fire. explosion or death!
Run gas supply line in accordance with all applicable codes.
Locate and install manual shutoff valves in accordance with state and local requirements.
3-C, GAS TABLE
Refer to Table (1) to size the supply piping to minimize pressure drop between meter or regulator and unit.
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3
Inch water Column
(TABLE 1) (Based on a 0.60 Specific Gravity Gas)
Nominal
Iron Pipe Internal Length of Pipe (Feet)
Size Diameter
(inches) (inches) 10 20 30 40 50 60 70 80 90 100 125 150 175 200.
3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55} BTU'S
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100} PER
1 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210} HOUR
1 1/2 L610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320} X1,000