Specifications

Ducted Split Type Air-Conditioning
24
Air supply
Air return
Suspender
Hook
Flat
washer
Spring
washer
Nut
Installation of suspender
>1000
>1000
>560
Fig.20 Schematic for the indoor unit
3) Drain hose
For easy drainage of the condensation water, the should be installed with a downward gradient. To avoid
the condensation, the connection pipe joint should be insulated with thermal insulation material. A water seal
should be employed as shown in Fig. 19 and the height of the water seal could be determined by the pressure of
the drain hose.
Drain hose is in negative pressure state: A = B P/10+20 (mm)
Drain hose is in positive pressure state: A 30mm,B P/10+20 (mm)
Note: P is the absolute pressure of the drain hose position, Pa
A
B
Drain hose
Water seal
4) Refrigerant pipe insulation layer
To avoid condensation of drew and water leakage, gas pipe and liquid pipe of refrigerant should be insulated
with thermal insulation material and adhesive tape.