User`s manual
M180-MLT350 Dehumidifiers
28
6 Product Design Information 190TGB-1034-A
6.5 Technical Specifications
Model ML180 ML270 MLT350
Process Air
1
Rated Airflow (m
3
/s)
Rated Airflow (m
3
/h)
Min. available static pressure (Pa)
2
Fan Motor power (kW) at 50Hz
3
Fan motor power (kW) at 60Hz
3
0,05
180
200
0,25
0,25
0,075
270
200
0,36
0,36
0,097
350
200
0,25
0,25
Reactivation Air
1
Rated Airflow (m
3
/s)
Rated Airflow (m
3
/h)
Min. available static pressure (Pa)
Fan Motor power (kW) at 50Hz
3
Fan motor power (kW) at 60Hz
3
0,019
67
200
-
-
0,027
99
200
-
-
0,019
67
200
-
-
Rated Current
Current (Amps/Phase) 1~ 50Hz 220V
Current (Amps/Phase) 1~ 60Hz 220V
Current (Amps/Phase) 1~ 50Hz 230V
Current (Amps/Phase) 1~ 50Hz 240V
Current (Amps/Phase) 3~ 50Hz 220V
Current (Amps/Phase) 3~ 60Hz 220V
Current (Amps/Phase) 3~ 50Hz 230V
Current (Amps/Phase) 3~ 60Hz 230V
Current (Amps/Phase) 3~ 50Hz 380V
Current (Amps/Phase) 3~ 60Hz 380V
Current (Amps/Phase) 3~ 50Hz 400V
Current (Amps/Phase) 3~ 50Hz 415V
Current (Amps/Phase) 3~ 60Hz 440V
Current (Amps/Phase) 3~ 60Hz 460V
Current (Amps/Phase) 3~ 60Hz 480V
Current (Amps/Phase) 3~ 50Hz 500V
9,9
9,9
9,5
9,2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
8,5
8,5
8,2
8,1
5,0
5,0
4,7
4,6
4,3
4,1
4,0
3,8
9,9
-
9,5
9,2
-
-
-
-
-
-
-
-
-
-
-
-
Reactivation Heater
Temperature increase across heater (°C)
Reactivation heater power (kW)
95
1,8
95
2,7
95
1,8
Miscellaneous Data
Drive Motor Power (W)
Air Filtration (Standard)
Dust and Water Resistance (Main Case)
Dust and Water Resistance (Electrical Controls)
Fan Motor Winding Insulation Grade
Drive Motor Winding Insulation Grade
High Temperature Cut-Out (°C)
5
EU3
IP44
IP54
Class F
Class F
160
± 5
5
EU3
IP44
IP54
Class F
Class F
160
± 5
5
EU3
IP44
IP54
Class F
Class F
160
± 5
Contactor Coil Voltage
Max. Noise Level Unducted (dBA)
24Vac
80 dBA
1
Figures quoted are nominal, based on fan inlet temperature of 20°C, and an air density of 1,2kg/m
3
.
2
Without optional F5 or F7 filter boxes.
3
ML180, ML270, MLT350 dehumidifiers have a single motor driving both process and reactivation air fans.
Table 6-2. Technical Specifications