User manual
(1) General
This unit employs many features previously unavailable in an industrial power supply. It has
been designed to withstand the high levels of interference found in heavy industry and has
emission levels low enough for it to be used in residential, commercial and light industrial
environments.
The Evolution 10-3x360-520/24 has a high level of reserve power. This enables loads with
significant inrush current to be supported and will also ensure that circuit breakers will trip in
event of short circuit.
A protective feature is provided which will take control as the unit approaches the power limit
due the overload or excessive temperature brought about by lack of ventilation.
If input voltage drops down to 3 x 300 VAC for 4 sec, output voltage still complies to PLC
standard EN 61131-2 (≥ 20,4 VDC).
Use only in star-architecture TN, TT and IT networks.
(3) Features
[1] Output terminal:
Conductor sizes
Solid 1,5 - 6 mm² / 15 - 9 AWG
Stranded 1,5 - 4 mm² / 15 - 11 AWG
Stranded with ferrule without / with plastic sleeve 1,5 - 4 mm² / 15 - 11 AWG
Ferrule minimum lenght must be
≥ 8mm
Wire insulation temperature rating 75°C.
Tightening torque: min. 0,5 Nm / 7 lb. in.
[2] Bi-colour LED, output voltage “OK” - green, overload - red.
[3] Output voltage adjust 22 - 28 VDC;
when over 24 VDC is used, must input voltage be accordingly higher.
[4] Input terminal:
Conductor sizes
Solid 1,5 - 6 mm² / 15 - 9 AWG
Stranded 1,5 - 4 mm² / 15 - 11 AWG
Stranded with ferrule without / with plastic sleeve 1,5 - 4 mm² / 15 - 11 AWG
Ferrule minimum lenght must be
≥ 8mm
Wire insulation temperature rating 75°C.
Tightening torque: min. 0,5 Nm / 7 lb. in.
(4) Location
The power supply is cooled by natural convection. Top and bottom clearances should be
50 mm at minimum. Evolutionthree phase power supplies can be used side by side without
any distance. The ambient temperature should be measured on the underside of the unit.
There will be an increase of 25°C at the top. If natural convection is restricted, forced
cooling should be used. Mounting should comply with EN 60950-1 point 4.7 and 4.6.1.
Protection class of the case IP20 (EN 60529).
(5) Mounting [7]
The rail should be fixed solidly so that it cannot twist when mounting or removing the unit.
Mounting instructions [5], Removing instructions [6].
(6) Switching on
Factory set, ready to use, check the connection diagrams for parallel and series
connection. Check the connection diagram for DC use [13].
(7) Loading capacity
The nominal current is 10 A but due to the nature of industrial loading, the power supply
has been designed to support loads with high inrush currents without damage or
shutdown. Curve [8] shows the typical voltage / current curve. Decreasing part of the
curve [8] shows the current limitation. Curve [9] shows the typical overload / temperature
limit. To ensure correct convection cooling, the unit must always be mounted with rail
horizontally. Power supply is designed to give 150% output power (power boost) for min.
4 seconds [10].
(8) Parallel connection [11]
Up to 5 units may be connected in parallel. The open circuit voltage of each unit should be
set to same value. Accuracy of setting will determine how well the units share the load
current. The gauge and lenght of the cable between each power supply and the common
point should be the same.
(9) Series connection
Up to 2 units may be connected in series to give either 48 VDC or +/-24 VDC. Check the
connection diagram [12].
(10) Using circuit breakers on the power supply output:
On the short circuit, the power supply will trip, for example, the following ABB-STOTZ
circuit breaker:
S201-C2A
S201-Z4A
(11) Standards
Electrical safety IEC / EN 60950-1 (CB Scheme), CSA, SELV
CSA C22.2 No 14, ANSI/UL508
EMC EN 61204-3 (2000): EMI: Class B, EMS: Industrial environment, GL
Immunity EN 61000-4-2 (1995) ESD 4/8 kV
EN 61000-4-3 (1996) Rf-field 10 V/m
EN 61000-4-4 (1995) EFT/B 2/2 kV
EN 61000-4-5 (1995), Surge 1/2 kV; 500 V
EN 61000-4-6 (1996) Cond. Rf 10 V
EN 61000-4-11
Emissions EN 55022 B, RF-emissions
EN 61000-3-2 (2006)
(valid with three phase use)
EN 61000-3-3 (1995)
EN 60204-1 60 V / 1 s
We reserve the right to change this specification.
EVOLUTION 3 PHASE 10
In order to take the best advantage of the
features that this power supply has to offer
and to ensure long term reliability for your
equipment, please read these instructions
carefully before installation and use. They
should be retained for future reference.
Evolution 10-3x360-520/24
Art. No. 85001
OPERATING INSTRUCTIONS
(2) Technical specification, Art. No. 85001
V1.3
Nominal voltage
3 x 360 - 520 VAC, 480 - 745 VDC
Input voltage range
3 x 324 - 572 VAC
Use allowed with two phases
2 x 340 - 572 VAC
Nominal frequency
50 / 60 Hz ±6%
Input current, I
nom.
0,8 A / 3 x 360 VAC - 0,5 A / 3 x 520 VAC
Input current with two phase
1,3 A / 2 x 360 VAC - 1,0 A / 2 x 520 VAC
Inrush current
< 15 A / 3 x 400 VAC after 1 ms
Efficiency, typ.
90% / 3 x 400 - 520 VAC
Power factor, typ.
0,6 / 3 x 400 VAC and 24 VDC / 10 A
External fuse max.
3x10A(T)
Safety class
1
Output voltage, adjustable 22 - 28 VDC
24 VDC
Static regulation accuracy
+/-1%
Dynamic regulation accuracy typ.
0->100%, 5% 1ms / 100%->5%, 5% 1ms
Start-up time
< 400 ms
Hold up time of the output
> 19 ms / 3 x 400 VAC and 24 VDC / 10 A
Output current, continuous
24 VDC - 10 A (+55°C) / 6,5 A (+70°C)
Output current, continuous
28 VDC - 8,3 A (+55°C) / 4,5 A (+70°C)
Output current (power boost)
15A/>4s
Output current, short circuit, typ.
11 A
Output ripple
<50mV
rms
Overloading / temperature protection
Yes
Overvoltage shutdown
< 35 VDC
Relative humidity
5 - 95% , no condensing
Operation temperature
-25°C - +70°C (> +55°C derating)
Storage temperature
-40°C - +85°C
Protection class, case, EN 60529
IP20
Dimensions W x H x D; Weight
93 x 132 x 114 mm; 1,3 kg
1
2
3
4
8
9
51015
12
10
8
6
4
2
0
5
6
7
9393
93
132
2
66
66
5
24 VDC
28 VDC
Uin 3x400VAC /
Uout 24 VDC - 10 A
(DC+/-24V)
(DC +/ - 24V)
DC48V
3x400 VAC
DC24V
Art. Nr. 85001
Art. Nr. 85001
Art. Nr. 85001
Art. Nr. 85001
Art. Nr. 85001
Art. Nr. 85001
Art. Nr. 85001
Art. Nr. 85001
11
12
PE
3x400 VAC
PE
50% 100% 150%
10
480-745 VDC
Art. Nr. 85001
Art. Nr. 85001
PE
+
-
L1
L2
L3
13
(+)
(-)
INPUT Y
3x360-520VAC
INPUT Y
3x360-520VAC
Output OK / Alarm
Uout Adj. 22 - 28V
OUTPUT
24V / 10ADC
OUTPUT
24V / 10ADC
Art. No. 85001
Evolution 10
L1
L2
L3
0.80 - 0.50A 50 - 60Hz
0.80 - 0.50A 50 - 60Hz
IP20 SELV
t-25...+55°C
Made in Czech Republic
IP20 SELV
t
-25...+55°C
Made in
Czech Republic
!
Read instruc-
tion manual
before use!
Read instruc-
tion manual
before use!
165828
95038-10HH
165828
95038-10HH