User manual

(1) General
This unit employs many features previously unavailable in an industrial power supply. It has
been designed to withstand the high levels of interference found in heavy industry.
The Evolution 40-3x360-520/24 has a high level of reserve power. This enables loads with
significant inrush current to be supported and will also ensure that circuit breakers will trip in
event of short circuit.
A protective feature is provided which will take control as the unit approaches the power limit
due the overload or excessive temperature brought about by lack of ventilation.
If input voltage drops down to 3 x 300 VAC for 4 sec, output voltage still complies to PLC
standard EN 61131-2 ( 20,4 VDC).
Use only in star-architecture networks.
(3) Features
[1] Output terminal:
Conductor sizes
Solid 2,5 - 16 mm² / 13 - 5 AWG
Stranded 2,5 - 16 mm² / 13 - 5 AWG
Stranded with ferrule without / with plastic sleeve 2,5 - 16 mm² / 13 - 5 AWG
Ferrule minimum lenght must be
10 mm
Wire insulation temperature rating 75°C
Tightening torque: min. 1,2 Nm / 11 lb. in.
[2] Bi-color LED, output voltage ”OK” – green, overload – red.
[3] Output voltage adjust 22 - 28 VDC;
when over 24 VDC is used, must input voltage be accordingly higher.
[4] Input terminal:
Conductor sizes
Solid 1,5 - 6 mm² / 15 - 9 AWG
Stranded 1,5 - 4 mm² / 15 - 11 AWG
Stranded with ferrule without / with plastic sleeve 1,5 - 4 mm² / 15 - 11 AWG
Ferrule minimum lenght must be
8mm
Wire insulation temperature rating 75°C
Tightening torque: min. 0,5 Nm / 7 lb. in.
(4) Location
The power supply is cooled by natural convection. Top and bottom clearances should be
50 mm at minimum. When used with maximum output power and high ambient
temperature (>50°C), front and side clearances shall be 100 mm minimum. The ambient
temperature should be measured on the underside of the unit. There will be an increase
of 25°C at the top. If natural convection is restricted, forced cooling should be used.
Mounting should comply with EN 60950-1 point 4.7 and 4.6.1. Protection class of the case
IP20 (EN 60529).
(5) Mounting [7]
The rail should be fixed solidly so that it cannot twist when mounting or removing the unit.
Mounting instructions [5], Removing instructions [6].
(6) Switching on
Factory set, ready to use, check the connection diagrams for parallel and series
connection. Check the connection diagram for DC use [13].
(7) Loading capacity
The nominal current is 40 A but due to the nature of industrial loading, the power supply
has been designed to support loads with high inrush currents without damage or
shutdown. Curve [8] shows the typical voltage / current curve. Decreasing part of the
curve [8] shows the current limitation. Curve [9] shows the typical overload / temperature
limit. To ensure correct convection cooling, the unit must always be mounted with rail
horizontally. Power supply is designed to give 150% output power (power boost) for min.
4 seconds [10].
(8) Parallel connection [11]
Up to 5 units may be connected in parallel. The open circuit voltage of each unit should be
set to same value. Accuracy of setting will determine how well the units share the load
current. The gauge and lenght of the cable between each power supply and the common
point should be the same.
(9) Series connection
Up to 2 units may be connected in series to give either 48 VDC or +/-24 VDC. Check the
connection diagram [12].
(10) Using circuit breakers on the power supply output:
On the short circuit, the power supply will trip, for example, the following ABB-STOTZ
circuit breaker:
S201-C6A
S201-Z16A
(11) Standards
Electrical safety IEC / EN 60950-1 (CB Scheme), CSA, SELV
CSA C22.2 No 14, ANSI/UL508
EMC EN 61204-3 (2000): EMI: Class B, EMS: Industrial environment
Immunity EN 61000-4-2 (1995) ESD 4/8 kV
EN 61000-4-3 (1996) Rf-field 10 V/m
EN 61000-4-4 (1995) EFT/B 2/2 kV
EN 61000-4-5 (1995), Surge 1/2 kV; 500 V
EN 61000-4-6 (1996) Cond. Rf 10 V
EN 61000-4-11
Emissions EN 55022 B, RF-emissions
EN 61000-3-2 (2006)
(valid with three phase use)
EN 61000-3-3 (1995)
EN 60204-1 60 V / 1 s
We reserve the right to change this specification.
EVOLUTION 3 PHASE 40
In order to take the best advantage of the
features that this power supply has to offer
and to ensure long term reliability for your
equipment, please read these instructions
carefully before installation and use. They
should be retained for future reference.
Evolution 40-3x360-520/24
Art. No. 85004
OPERATING INSTRUCTIONS
(2) Technical specification, Art. No. 85004
V1.1
Nominal voltage 3 x 360 - 520 VAC, 480 - 745 VDC
Input voltage range 3 x 324 - 572 VAC
Use allowed with two phases (*) 2 x 360 - 572 VAC
Nominal frequency 50 / 60 Hz ±6%
Input current, I
nom.
2,4 A
rms
/ 3x360 VAC - 1,7 A
rms
/ 3x520 VAC
Inrush current none
Efficiency, typ. 91% / 3 x 400 VAC - 90% / 3 x 520 VAC
Power factor, typ. 0,70 / 3 x 400 VAC and 24 VDC / 40 A
External fuse max. 3 x 20 A / 250 VAC, type B or C
Safety class 1
Output voltage, adjustable 22 - 28 VDC 24 VDC
Static regulation accuracy +/-1%
Dynamic regulation accuracy typ. 0->100%, 5% 1ms / 100%->5%, 5% 1ms
Start-up time < 500 ms
Hold up time of the output > 10 ms / 3 x 400 VAC and 24 VDC / 40 A
Output current 24 VDC / +55°C 40 A
Output current 28 VDC / +55°C 34 A
Derating +55°C - +70°C, -0.67A / °C
Output current (power boost) 60 A / > 4 s
Output current, short circuit, typ. 45 A
Output ripple < 50 mV
rms
Overloading / temperature protection Yes
Overvoltage shutdown < 35 VDC
Relative humidity 5 - 95% , no condensing
Operation temperature -25°C - +70°C (> +55°C derating)
Storage temperature -40°C - +85°C
Protection class, case, EN 60529 IP 20
Dimensions W x H x D; Weight 164 x 132 x 142 mm; 3,0 kg
(*) Check diagram [14] for derating values.
1
2
3
4
8
9
10 20 30 40 50
50
40
30
20
10
0
5
6
7
164
132
2
66
66
5
50% 100% 150%
10
24 VDC
28 VDC
Uin 3x400VAC /
Uout 24 VDC - 40 A
480-745 VDC
Art. No. 85004
Art. No. 85004
PE
+
-
L1
L2
L3
13
(+)
(-)
(DC+/-24V)
(DC +/ - 24V)
DC48V
3x400 VAC
DC24V
Art. No. 85004
Art. No. 85004
Art. No. 85004
Art. No. 85004
Art. No. 85004
Art. No. 85004
Art. No. 85004
Art. No. 85004
11
12
PE
3x400 VAC
PE
14
-5 15 35 55 75
A
B
C
40
30
20
10
0
-25
(°C)
(A)
A: 2x360...460VAC
B: 2x460...560VAC
C: max. 60 s
Uout 24 VDC
165828
Output OK / Alarm
Output OK / Alarm
INPUT Y
3x360 - 520VAC
INPUT Y
3x360 - 520VAC
OUTPUT
24V / 40 ADC
OUTPUT
24V / 40 ADC
Art. No. 85004
Evolution 40
L1
L2
L3
2.40 - 1.70A 50 - 60Hz
2.40 - 1.70A 50 - 60Hz
IP20 SELV
t -25...+55°C
Made in Finland
IP20 SELV
t -25...+55°C
Made in Finland
!
Read instruc-
tion manual
before use!
Read instruc-
tion manual
before use!
Uout Adj. 22 - 28V
Uout Adj. 22 - 28V
165828