User manual
Emparro 10-100-240/24
85441
Emparro 1 PHASE
100-240 VAC
DC24V
Art. No. 85441
Art. No. 85441
PE
L
N
L
N
123
65
5,5
61,5
61,5
12,5
[1]
[2]
[3]
[4]
[5]
[9]
(DC +/ -24 V)
DC48V
Art. No. 85441
Art. No. 85441
100-230 VDC
Art. No. 85441
PE
+
-
(+)
(-)
100-240 VAC
PE
L
N
L
N
L
N
[12]
[13]
[14]
1.
1.
2.
[7] [8]
[6]
40
40
> 40
> 100
100
100
75
[11]
[10]
24
28
24
16
8
0
28
0 2 4 6 8 10 12
9,5
Art. No.
OPERATING INSTRUCTIONS
In order to take the best advantage of the
features that this power supply has to offer and to
ensure long term reliability for your equipment,
please read these instructions carefully before
installation and use. They should be retained for
future reference.
Documents downloaded by the EDP system and/or printed out
have only an informative character and are not subject to the updating service
We reserve the right to change this specification Refer to protection notice ISO 16016
(B) Technical specification
(A) General
This unit employs many features previously unavailable in an industrial power supply. It has
been designed to withstand the high levels of interference found in heavy industry.
It has a high level of reserve power. This enables loads with significant inrush current to be
supported and will also ensure that circuit breakers will trip in event of short circuit.
A protective feature is provided which will take control as the unit approaches the power
limit due to the overload or excessive temperature brought about by lack of ventilation.
Use only in star-architecture TN, TT and IT networks.
Unless otherwise specified, the measured values referring to an ambient temperature of 25°C,
nominal input voltage of 230 VAC and load of 24 VDC at 10A.
(B)Technical specification, Art. No. 85441
V1.7
Nominal voltage, U
Input voltage range
Nominal frequency
Input current,
Input
I
Inrush current
Efficiency
Power factor
Recommended external fuse max.
Recommended circuit breaker
Internal device protection
Protection class
Output voltage, U
Output voltage, adjustable 24 - 28 VDC
Start-up time
Input failure bridging
Output current, I 24
Output current, I 28
Output current (Power Boost)
Output current (Hyper Boost)
Short circuit
Ripple / Spikes
Overloading / Temperature protection
Climatic environmental conditions,
Input
N
N
N
VDC
VDC
Relative humidity
Ambient temperature
Storage temperature
Protection class, case,
Dimensions W x H x D; Weight
EN 60721
EN 60529
100 - 240 VAC, 100 - 230 VDC
85 - 265 VAC, 90 - 250 VDC
50 / 60 Hz ±6%
I / I : 1,8 A I²t: 0,5 A²s
94,3 %
0,95
20 A (T) In building installation
C4
6,3 A (T)
I
24 VDC
Factory setting: 24,1 VDC ±0,2 V
< 400ms @ U 100-230 VAC
10 A up to +60°C
8,5 A up to +60°C
I
I x 450% for min. 20ms @ 60°C
< 50 mV / < 200 mV
Yes
3K3
5 - 95% , no condensing
123 x 65 x 138; 0,85 kg
2,4A @ 110 VAC/DC - 1,2A @ 230 VAC/DC
30 ms @ U 100 VAC; Last 24 VDC/10A
x 150% für min. 4s, without voltage variation
After "Power Boost" follows constant current: 10 A
rms rms
eff RMS
Input
Input
N
N
eff ss
≥
-25°C - +60°C
-40°C - +85°C
IP 20
(E) Mounting [9]
(F) Switching on
(G) Loading capacity
(H) Parallel connection [12]
(I) Series connection [13]
(J) Using circuit breakers on the power supply output
(K) Standards
Electrical safety IEC / EN 60950-1, SELV
EN 60204-1, 60 V / 1 s
SEMI F47 – 0706, requirements complied / proof ( 160 VAC)
EMC EN 61204-3
Emissions EN 55011 Class B; Group 1,
EMI: Class B;
EMS: Industry area
EN 61000-3-2
EN 61000-3-3
≥
Immunity EN 61000-4-2 ESD, Contact +/- 6 kV; Air +/- 8 kV
EN 61000-4-3 Rf-field, 10 V/m
EN 61000-4-4 Burst, +/- 2 kV, 5/50 ns
EN 61000-4-5 Surge,
EN 61000-4-6 Cond. Rf, 10 V
EN 61000-4-11
AC Input L1 N (DM) / L1 N PE (CM) ±1 kV/ ±2 kV/ ±4 kV
DC Output (+) (-) (DM) / (+) (-) PE (CM) ±0,5 kV/ ±0,5 kV
àà
àà
Ú
Ú
(D) Location
2,5 mm / 0,1 in
[1]
[2]
Output terminal:
Conductor sizes
Solid 1,0 - 10 mm² / 17 - 8 AWG
Stranded 1,0 - 6 mm² / 17 - 10 AWG
Stranded with isolated ferrule 1,0 - 4 mm² / 17 - 12 AWG
Stranded with ferrule 1,0 - 6 mm² / 17 - 10 AWG
Wire insulation temperature rating 75°C.
Potential free alarm contact (13/14), 60 VDC / 50 mA max. (resistive load) SELV:
Output voltage „OK“ = closed, „Alarm“ = open.
Potentiometer for output voltage 24 - 28 VDC.[4]
[3]
[5]
Bi-colour LED: output voltage „OK” = green, „Alarm“ = red.
Input terminal:
Conductor sizes
Solid 0,75 - 4 mm² / 18 - 12 AWG
Stranded 0,75 - 2,5 mm² / 18 - 14 AWG
Stranded with isolated ferrule 0,75 - 1,5 mm² / 18 - 16 AWG
Stranded with ferrule 0,75 - 2,5 mm² / 18 - 14 AWG
Wire insulation temperature rating 75°C.
The rail should be fixed solidly so that it cannot twist when mounting or removing the
unit. Mounting instructions [7], Removing instructions [8]. To ensure correct convection
cooling, the unit must always be mounted with rail horizontally.
Factory set, ready to use, check the connection diagrams for parallel and series
connection. Check the connection diagram for DC use [14].
The nominal current is 10 A but due to the nature of industrial loading, the power supply
has been designed to support loads with high inrush currents without damage or
shutdown. Curve [10] shows the typical voltage / current curve. Decreasing part of the
curve [10] shows the current limitation. Power supply is designed to give 150% output
power (Power Boost) for min. 4 seconds [11].
Up to 5 units may be connected in parallel. The open circuit voltage of each unit should
be set to same value.
1) Accuracy of setting will determine how well the units share the load current.
2) On secondary side the cross section and length of the cable should be the
same.
Max. 2 units in series to guarantee the SELV output. With more than 2 units in series,
the output voltage will exceed the SELV limits.
On the short circuit, the power supply will trip, for example, the following circuit breaker:
- ABB S201-C6 (for 2m, 2,5 mm², wire / without load)
(C) Features
The power supply is cooled by natural convection. See in picture .
one phase power supplies can be used with a distance of 6 mm to each other.
at the bottom side
There will be an increase of 25°C at the top. If natural convection is restricted, forced
cooling should be used. Mounting should comply with EN 60950-1 point 4.7 and 4.6.1.
Protection class of the case IP20 (EN 60529).
[6]
Emparro
Please note: The ambient temperature is to measur of the unit.