User manual
3
2
MB Cap Ultra 10/24 1A/380S - 85467
MB Cap Ultra 10/24 1A/380S - 85467
Lifetime of the
capacitors
The lifetime of the capacitors is
temperature-dependent!
End of lifetime is reached when the
buffering time has fallen to 70% of the
rated buffering time.
10
20
30
40
Temperature in °C
50
60
70
10
20
30
40
50
60
70
0
Year
Connection
Before installation the data of the DC supply have to be compared with the data on the type plate
and checked for compliance. Connection according to the indications of the terminals (see simplified
diagram and configuration).
In case of overload the DC output current is composed of the max. current of the
buffering module and the current from the supplying DC mains. In order to avoid
overloading of the DC output circuit external protection is required! (For values please
refer to “Technical data”)
Signal connections
Indications and signal outputs:
Operating modes Status LED Output
Operation LED green, lights up:
Presence system voltage at terminal
U respectively as long as the
internally supplied with energy.
U OK LED green, lights up:
- Presence external supply,
U>U
U . > LED green, lights up:
Energy in capacitor > 80%
LED green, goes off:
Energy in capacitor > 30%
(Values refer to standard
parameterization)
Default LED red, lights up:
- Overload at internal capacitor two-way
- Over- or undervoltage at
'U '
- Over current at output
Input
in
Input SYSTEM
cap
Input
1)
1)
1)
-
unit is
Potential-free relay contact,
normally open (NO),
i.e. max. contact load 30 V DC/ 0.5 A
Potential-free relay contact,
normally open (NO),
max. contact load 30 V DC/ 0.5 A
Potential-free relay contact,
contact (NO/NC),
max. contact load 30 V DC/ 0.5 A
terminal
I/O
1-9
USB
LED
Input
Output
Connection Terminal S
DC-input 'U ' +, -
DC-output (load) 'U ' +, -, -
Control input Shut-Down 'I/O' 1+/2-
Signal 'Uin OK' 'I/O' 3 / 4
Signal 'Ucap. >' 'I/O' 5 / 6
Signal 'Default': 'I/O' 7=COM, 8=NO,
9=NC
PC Interface USB
Input
Output
pring clamp
max. AWG 13
max. AWG 17
max. 2.5 mm²
max. 1 mm²
=COM =NO
=COM =NO
6mm
Software Manual computer / USB - Interface
www.murrelektronik.com
and for are downloadable on our
homepage.
Simplified diagram
1)
The alarm contacts are coupled with the LED displays. When the LED lights up the alarm
contact is closed.
Signal inputs:
Operating modes Status LED Output
Shut-Down Stop of buffer operation Potential-free connecting input,
switching level: 24 V DC (6-45 V DC)
Set-up
The unit is switched-on by connecting the DC supply to the terminal 'U '.Input
If the units are used in installations that require overloads for testing (e.g. acc. to
EN60204-1 / VDE0113 Part 1 19.4 Voltage test) the unit has to be separated from the
test set-up before voltage is applied.
(Original text EN60204-1 Components that are not designed for this test voltage have
to be disconnected during the test.)
Check if the connections are correct before first start-up. Establish electrical
connections only when the installation is disconnected from the supply.
Operation
The unit is supplied with energy for charging the capacitors and for supplying the loads (terminal
U ) from the input voltage (Terminal U ). Loads connected in parallel to the input terminal
are not buffered, as they are decoupled via the diode D1 (see “simplified diagram”). Therefore, the
power supply unit can feed additional unbuffered loads. Because of the flow voltage of diode D1
the supply voltage for charging the buffer module should be at least 0.7 V higher than the system
voltage.
After the .U has been switched on the supply voltage is measured and the corresponding
Output Input
Input
When operating the connected power supply > 24 V lifetime will decrease.
F
30V DC/0.5A
K1
2
LAST
US B
5
6
4
7
9
K
K
30V DC/0.5A
K
DC-DC-converter
LED4
Operation
D1
J1
1
30V DC/0.5A
LED3
μC
C1
I/ O
8
3
LED1
LED2
UOutput
UInput
SHUT-DOWN
UOKin
Ucap. >
Default
+
-
-
+
+
-
-
Murrelektronik GmbH
Postfach 1
165
D-71567 Oppenweiler
Telefon +49(0)7191/47-0
Falkenstraße 3
D-71570 Oppenweiler
Telefax +49(0)7191/47-130
Info@murrelektronik.com
http://www
.murrelektronik.com
Murrelektronik GmbH Postfach 1165 D-71567 Oppenweiler Telefon +49(0)7191/47-0
Falkenstraße 3 D-71570 Oppenweiler Telefax +49(0)7191/47-130
Info@murrelektronik.com http://www.murrelektronik.com