DATA SHEET
a 31.08.09 Pan
n
Control input 10.09.10
ri n 13.09.10 Sen
k
MICO 4.6
m
Verlustleistung 01.07.10
ri Ges. 4 channel
l
Überarbeitet 07.04.10
as
k
UL-Sicherungswerte 01.10.09
sb
sheet
j
URZeichenUL2367 25.05.09
ri
Art.-No.: 9000-41034-0100600
1
Idx. Änderun
g
Datu
m
Nam.
3Bl.
a Erstausgabe
15.04.05
DR
Dateiname 9000-41034-0100600_db_e_n
Technische Änderungen vorbehalten / We reserve the right to change this specification Schutzvermerk ISO 16016 beachten / Refer to protection notice ISO 16016
Vom EDV-System heruntergeladene bzw. ausgedruckte Dokumente besitzen informativen Charakter und unterliegen nicht dem Änderungsdienst / Documents downloaded by the EDP system and/or printed out have only an informative character and are not subject to the updating service
Functional description:
MICO 4.6 is a 4-channel electronic auxiliary circuit
switch and serves as current monitoring. The
operating voltage (+24V DC / at least 10A) is divided
into 4 current monitored load circuits (channels). By
applying the operating voltage the switched-on
channels are time-delay activated (time-delay of each
channel = 75 ms) to avoid overload current. The
current selector switches (1) enable an independent
setting of the operating currents of 1A, 2A, 4A or 6A
(see disconnecting characteristic). When exceeding
the operating current the corresponding channel will
be disconnected pursuant to the disconnecting
characteristic. In the event of voltage dip or power
failure the current operating condition will be saved
and reestablished after the recovery of the supply
voltage. The setting of the current range during
operation leads to the disconnection of the channel. It
may only be switched on manually. Each channel may be manually connected or disconnected through the buttons (2).
The current operating condition is signalled by the LED (2) – (red/green, see displays). All channels disconnected due
to overload may be activated through ON (restart) (3) – see restart. In addition, the module is provided with a
potential-free message output (4) to establish a summation message (see control output). A bridging concept permits
the lining-up of multiple modules (maximum operating current 40A) without wiring. For this purpose a bridging set is
available as an option.
Technical data:
Input values:
input voltage 24V DC, 18 ... 30V DC (SELV/ PELV)
input current (operating current) ca. 50mA, U = 24V
residual ripple of power supply < 5% for one-phase, 2% for three-phase
Frequency of power “on / off” max 0,5 Hz
overvoltage protector suppression protector 36V
maximum operating current (full load) max. 24A (0…+20%)
maximum operating current (bridging set) max. 40A
polarity No reverse polarity protection
Control input:
input voltage (ON-Restart) 10V ... 30V, (I = 5 ... 6mA)
function all branch circuits switched off by overcurrent or
short-circuit are switched on by rising edge
minimum pulse duration 0V: 1s
24V: 20 ms
overvoltage protector suppression protector 36V
Output values:
nominal output voltage corresponding to the input voltage
voltage drop at 6A per each load branch typ. 0,2 V
power loss per each load branch typ.: 0,2 W at 1 A; 0,4 W at 2 A; 0,8 W at 4 A;
1,2 W at 6 A
operating canel current (full load) max. 6A (-10…+20%)
output current OUT1 - OUT4 adjustable to 1, 2, 4 or 6A with rotary switch
overvoltage protector suppression protector 36V
overload protection see disconnecting characteristic
Wiring diagram:
Operating
voltage
+24V DC
Summation message (4)
Button (On / Off)
with status LED (2)
Current selector
switch (1)
Controlled
switch outputs
OUT1 – OUT4
ON (Restart) (3)
Earth (GND)
Operating
voltage
+24V DC
Earth (GND)
Module anchorage to
the bridging (9)
Bridging 16 mm² (7)
Bridging 4 mm² (8)
Bridging ON (6)
Summation message (5)
ON 14
ON 13