User manual
Installation instructions V2.3 Murrelektronik Intelligent Current Operator Installation instructions V2.3 Murrelektronik Intelligent Current Operator
MICO 4.6 Art.-No.: 9000-41034-0100600 MICO 4.6 Art.-No.: 9000-41034-0100600
Vom EDV-System heruntergeladene bzw. ausgedruckte Dokumente besitzen informative n Charakter und unterliegen nicht dem Änderungsdienst /
Documents downloaded by the EDP system and/or printed out have only an informative character and are not subject to the updating service
Technische Änderungen vorbehalten / Schutzvermerk ISO 16016 beachten /
We reserve the right to change this specification Refer to protection notice ISO 16016
Technical data:
Input values: Signalling: See “Displays“
Input voltage: Environment:
+24 V DC (SELV/ PELV) Storing temperature: -40°C to +80°C
Residual ripple of power supply Environmental temperature: 0 to +55°C
< 5% for one-phase, 2% for three-phase Cooling by natural convection
Range of working voltage Safety:
18-30 V DC Rated insulation voltage: 50V
Frequency of power ON/OFF max 0,5Hz degree of pollution: 2
Suppression protector 36 V Classification of over-voltage III
No reverse polarity protection Additional output protection:
Total operating current: 24 A (-10 to +20%) 6,3A fuse for each channel internal
(UL 248-14, UL File E10480).
Maximum summation current of +24 V Regulations:
terminals: 40 A EN 60529: Protective system - IP20
Output values: EN 61000-6-2:
Nominal output voltage: Immunity to interference class A
24V DC, corresponding to the input voltage EN 61000-6-3:
Voltage drop at 6A per each load branch: Interference emission class B
typical 0,2 V EN 60068-2-6: Oscillating test
Turn ON capacity: EN 60068-2-27: Shock test
max. 20 mF* Weight: ca. 160g
Internal fuse: 6,3 A delay fuse for each channel Measurements LxWxD: 90x70x80 mm
* Dependent on: component tolerance, conduit length, used power supply, load current, selected current range
Schematic circuit diagram:
Notice:
Please pay attention to the wire capability in relationship of its cross section, ambient temperature, current as
well as the used protection.The in 4 levels settable channel current serves as the wire protection and device
protection conform to EN60204-1, referring to the maximal permissible channel current. For lucid reasons
this installation instructions does not contain detailed information to all types of this product and may not
consider each fictitious case of erection, operation or installation. Continuing information may be taken from
the data sheet or from our homepage in the internet
http://www.murrelektronik.com
.
Technical alterations are reserved at any time.
© 2009 Murrelektronik GmbH, Oppenweiler
All rights reserved. Each reprint, even in parts, requires our written consent.
Murrelektronik GmbH P.O. Box 1165 D-71567 Oppenweiler Telefon +49(0)7191/47-0
Falkenstrasse 3 D-71570 Oppenweiler Telefax +49(0)7191/47-130
info@murrelektronik.com http://www.murrelektronik.com
MICO 4.6 Art.-No. 9000-41034-0100600
Installation instructions
Wiring diagram:
Functional description:
MICO 4.6 is a 4-channel electronic auxiliary circuit switch and serves as current monitoring. The operating
voltage (+24V DC/at least 10A) is split into 4 current monitored load circuits (channels). When engaging the
operating voltage the switched-on channels are time-delay activated (time-delay of each channel = 75 ms) to
avoid overload current. The current selector switches (1) enable an independent setting of the operating
currents of 1A, 2A, 4A or 6A (see disconnecting characteristic). When exceeding the operating current the
corresponding channel will be disconnected pursuant to the disconnecting characteristic. In the event of
voltage dip or power failure the current operating condition will be saved and reestablished after the recovery
of the supply voltage. The setting of the current range during operation leads to the disconnection of the
channel. It may only be switched on manually. Each channel may be manually connected or disconnected
through the buttons (2). The current operating condition is signalised by the LED (2) – (red/green, see
displays). All channels disconnected due to overload may be activated through ON (restart) (3) – see restart.
In addition, the module is provided with a potential-free message output (4) to establish a summation
message (see summation message). A bridging concept permits the lining-up of multiple modules (maximum
operating current 40A) without wiring. For this purpose a bridging set is available as an option (see bridging
set).
Bridging set: The bridging set minimises the efforts of wiring if multiple modules are joined together.
It offers the possibility of bridging the following potentials:
+24V DC (7), GND (8), ON (6) and summary message (5). A connecting piece is necessary to anchor both
modules (9). The bridging set is optionally available under:
item no.: 9000-41034-0000001 (packing unit 10 pieces)
item no.: 9000-41034-0000002 (packing unit 1 pieces)
-1-
Operating
voltage
+24V DC
Summation message (4)
Button (On / Off)
with status LED (2)
Current selecto
r
switch (1)
Controlled
Switch outputs
OUT1 - OUT4
ON
(
Restart
)
(
3
)
Earth (GND)
Operating
voltage
+24V DC
Earth (GND)
Bridging
16 mm² (7)
Bridging
4 mm² (8)
Bridging ON (6)
Summation message (5)
Module anchorage to
the bridging (9)
Reset
Control Logics
Load
1
24V DC
+24GND
Message 1-4
OUT
123
4
1413
Button
Load
2
Load
3
Load
4