Specification

Murray Electrical Products
Siemens Energy & Automation, Inc.
Alpharetta, Georgia U.S.A.
Rainproof Combination Metering
20 lb in
25 lb in
35 lb in
#10-14 Cu/
#10-12 Al
#8
#4-6
Neutral bar
See Markings on breakerBranch breaker
terminals
120 lb in1/0-#14N4
275 lb in250 kcmil- #4N3
275 lb in250 kcmil - #6N2
50 lb in
45 lb in
40 lb in
35 lb in
#2-#3
#4-#6
#8
#10-#14
N1
275 lb in250 kcmil - #6A, B
TorqueWire SizeTerminal
Accessories
Filler Plate Cat. No. QF3
If hub is required, the catalog numbers listed below
may be used on this enclosure
Trade size (in) Catalog number
1 ¼” RX125
1 ½” RX150
2” RX200
2 ½” RX250
General Information:
Remove twistouts from deadfront only where breakers
will be installed. All openings must be filled with
breakers or filler plates.
Circuit Breaker overload trip position is indicated by
handle position midway between ON and OFF. To reset,
move handle to OFF position then turn ON.
For installation in accordance with all local Electrical codes
and/or the National Electrical Code .
Short Circuit Current Rating (Watthour Meter not included in short circuit rating)
The panelboard has a maximum short circuit rating of 22,000 RMS symmetrical amperes, 120/240 volts ~. The actual rating is equal
to the lowest rating of any breaker installed. Any circuit breaker replaced or added in this panelboard must be manufactured by
Siemens or Murray and must be the types listed below.
Part No. 4099558 Rev C
J2
E10703
A
B
N1
N2
N3
N4
SERVICE
DISCONNECTS
BONDED
NEUTRAL
1
2
4
3
Catalog number
JC0406L1200H
Panelboard Rating
200 Amps, Max
120/240 Volts ~, 1 phase, 3 wire
208Y/120 Volts ~, 1 phase, 3 wire
(Derived from 3 phase – 4 wire system)
Meter Socket Rating
200 Amps Continuous
Suitable Only For Use As
Service Equipment
Only single pole circuit breakers rated
greater than 30 amps may be used to
comply with Lighting and Appliance
Panelboard requirements.
For Overhead or Underground
Service
Use 60/75° C Copper or
Aluminum Conductor
in Terminals
A, B, N1, N2, N3, and N4.
1 __________________________________
2 __________________________________
3 _________________________________
---------------------------------------------------------
4 _________________________________
--------------------------------------------------------
Enclosure
Type 3R
Top two twistouts for
Type QNH or MD-HT
circuit breakers only
Important
This equipment has been designed for use only with Murray Type, MP-T, MP-GT, MP-HGT, MP-HT, MH-T, MP-AT,
MP-HAT, MP-ET, MP-HET, MD-HT, MD-T or Siemens Type QP, QT, QPF, QPHF,QE, QEH, QAF, QAFH, QN,
or QNH Circuit Breakers. Use of other circuit breakers in this equipment will void the warranty.
Do not spray or allow any petroleum based chemicals, solvents, or paint to contact interior components.
The National Electrical Code is a recognized trademark of National Fire Protection Association.
Assembled in Mexico
May 30, 2003