Specification

Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog
3-34
3
MURRAY Group Metering
Line Terminal Kits
Line terminals are available in kits of
4 terminals each. The terminals are
tang lugs which mount on threaded
studs provided on the phase blocks.
Terminals are available in 3 sizes:
n (1) 350 kcmil
n (1) 500 kcmil
n (2) 500 kcmil maximum
Breaker Troughs
Breaker troughs are horizontal indoor
wireways that contain provisions for
plug-in circuit breakers used as tenant
mains. The trough bolt to the top of
the meter stacks. Field wiring connects
each meter socket to a circuit breaker
mounting block. Breaker troughs are
available in 2 to 5 stack postitions and
can be ganged to accommodate 6 or
more stacks. Trough end walls are
ordered separately.
Circuit Breakers
New York City Apartment Metering
uses standard 2-pole plug-on circuit
breakers, Murray Type MP-T, 100 amps
maximum.
End Wall Kits
These kits contain 4 end walls; 2 end
walls for the line trough and 2 end walls
for the breaker trough.
Coupler Kits
These kits each contain 2 trough cou-
pler straps; one for the line trough and
one for the breaker trough. These cou-
plers mount using the same mounting
screw holes as the end walls.
Line Trough Spacer Kits
These kits may be used to increase
wire bend space between the first
phase block and line entrance end
wall, if necessary. They connect to line
troughs with a standard coupling kit.
Trough end walls are ordered sepa-
rately.
Getting Started
Before ordering components, the following should be known:
n Installation instructions are shipped with the product
n Number of meter positions
n Amp rating of each meter position
n Voltage and phase of incoming line
n Line conductor size and quantity
n Vertical and horizontal space limitations, if any
Meter stacks are 10” wide and are 10” high for each meter position, or blank position.
(A 3-high stack with no blank postions would be 10” wide and 30” high). When consider-
ing the overall height of an installation, you must add the height of the line trough (12”)
and the breaker trough (16”) to the stack height.
An installation of 3-high stacks would be 58” in overall height (30” + 12” + 16” = 58”).
All meter stacks in the same meter bank must be the same height to allow the breaker
trough to fit on top of the stacks.
Group Metering: NYC Gangable Metering
General Information