Specification
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog
3-37
3
MURRAY
Group Metering
Line Terminals
(Use Specification Chart #5)
Knowing the size and quantity per
phase of the line conductors, select and
spec these from Specification Chart #5.
Line terminals come in kits of four ter-
minal each. One kit will supply line ter-
minals for three phase legs and neutral.
End Walls
(Use Specification Chart #6)
NOTE: Each installation MUST have
an end wall kit! The kit provides end
walls for each end of the line and
breaker troughs. (Four end walls). Use
Specification Chart #6.
Coupling Kits
(Use Selection Chart #2 and
Specification Chart #6)
When more than one line trough is
needed to support the number of
meter stacks on a job, or when a line
trough spacer is required, coupling
straps are required to connect the
troughs. Use Selection Chart #2 foot-
notes 3 and 4 to determine quantity
of coupling kits required. Each kit pro-
vides one strap for line trough and one
strap for breaker trough. Spec from
Specification Chart #6.
Line Trough Spacer Kits
(Use Selection Chart #2 and
Specification Chart #6)
In some applications, the first phase
block may be too close to the end wall
of the line trough to provide proper wire
bend space for the line conductors being
used. Selection Chart #2 footnotes 1
and 2 will show when spacer kits are
required.
Tenant Circuit Breakers
Each meter position in use requires a
tenant circuit breaker. Use standard
Murray Type MP-T circuit breakers from
the Murray Catalog.
Specification Chart #5—Line Terminals
Wire Range Catalog Number
(1) #6-350 kcmil
ULK1350
(1) #4-500 kcmil or
(2) #1/0-250 kcmil
ULK1500
(2) #2-600 kcmil
ULK2500
Specification Chart #6—End Wall and Coupling Kits
Item Catalog Number
End Wall Kit
Contains 4 end walls; 2 for line
trough and 2 for breaker trough.
UEW1216
Coupling Kit
Contains 2 coupling straps; 1 for line
trough and 1 for breaker trough.
UCP1216
Specification Chart #7—Accessories
Item Catalog Number
Spacer
10” spacer for use with line trough to
provide wire bend space where required
ULT10SP
Meter Cover
UMCVR
Blank Position Cover
UMBCVR
Plastic Meter Cover (Ring Type)
SX087M
Breaker Filler Plate
LX100FP
Group Metering: NYC Gangable Metering
Terminals & Accessories
Product Category RESI