Use & Care Guide

Catalog Number
LW1224B1100 -
Type 3R
Model Enclosure
RATINGS:
125A MAXIMUM - SEE MAIN BREAKER RATING IF USED.
BACK-FED BREAKER REQUIRES HOLD-DOWN KIT MBR2M.
120/240 V~, 60 HZ, 1Ø 3W
208Y/120 V~, 60 HZ, 1Ø 3W
SUITABLE ONLY FOR USE AS SERVICE
EQUIPMENT UNLESS CONVERTED FOR USE IN NON-SERVICE
EQUIPMENT APPLICATIONS BY THE INSTALLATION OF MURRAY INSULATED NEUTRAL TERMINAL
KIT INSNB27.
WHEN USED AS SERVICE EQUIPMENT, UNUSED NEUTRAL BAR TERMINALS MAY BE USED TO
TERMINATE EQUIPMENT GROUNDING WIRES IN THE COMBINATIONS INDICATED FOR
EQUIPMENT GROUND BAR TERMINALS.
SUM OF MH-T BREAKER RATING IS NOT TO EXCEED 110 AMPS PER BRANCH CIRCUIT BUS STAB.
TO RESET BREAKERS WITH TRIPPED HANDLE POSITION BETWEEN "ON" AND "OFF", MOVE
HANDLE TO "OFF" THEN TO "ON".
REMOVE TWISTOUTS FROM TRIM ONLY WHERE BREAKERS WILL BE INSTALLED. ALL
OPENINGS MUST BE FILLED WITH BREAKERS OR FILLER PLATES. USE ONE MBF125M FILLER
PLATE TO FILL 100-125A MAIN BREAKER OPENING.
Outdoor Load Center
Hazardous Voltage.
Will cause death, serious injury
or substantial property damage.
Turn off power supplying this
equipment before working inside.
PELIGRO
DANGER
Desconecte el suministro de energía a este
equipo antes de trabajar en su interior.
Voltaje peligroso. Causará la
muerte, lesiones graves o daño
substancial a la propiedad.
IMPORTANT: DO NOT ALLOW PETROLEUM BASED (HYDROCARBON) SPRAYS, CHEMICALS, SOLVENTS
OR ANY PAINT TO CONTACT INTERIOR COMPONENTS. PETROLEUM BASED CHEMICALS CAN CAUSE
DEGRADATION OF ELECTRICAL INSULATING MATERIALS.
Murray Electrical Products
Siemens Energy & Automation, Inc.
Alpharetta, Georgia U.S.A.
T
4099726 Rev.A
OO
USE COPPER OR ALUMINUM 60 /75 C WIRE
SEE BREAKER MARKINGS FOR WIRE SIZE AND TORQUE REQUIREMENTS.
EQUIPMENT GROUND BAR
TERMINALS ARE SUITABLE FOR THE FOLLOWING WIRE COMBINATIONS:
SMALL TERMINALS: ONE 14 TO 6 AWG CU; ONE 12 TO 6 AWG AL; TWO 14
AWG CU; TWO 12 AWG CU; TWO 12 AWG AL SOLID WIRES.
LARGE TERMINALS: ONE 14 TO 2 AWG CU; ONE 12 TO 2 AWG AL; TWO OR
THREE 14 AWG CU; TWO OR THREE 12 AWG CU OR AL; TWO 10 AWG CU;
TWO OR THREE 10 AWG AL; THREE 10 AWG CU SOLID WHEN TORQUED TO 50
LB-IN; THREE 10 AWG CU STRANDED.
A, B 110 LB-IN
NEUTRAL AND EQPT GROUND BAR
LX081M NEUTRAL
LUG KIT
WIRETERMINALS TORQUE
2/0 - 4 AWG
SMALL TERMINALS 10 - 14 AWG
8 AWG
6 AWG
20 LB-IN
25 LB-IN
35 LB-IN
LARGE TERMINALS
10 - 14 AWG
8 AWG
1/0 - 6 AWG
35 LB-IN
40 LB-IN
45 LB-IN
2/0 - 6 AWG 50 LB-IN
MAIN LUG/MAIN BRKR TO BUS
CONNECTION (1/4-20 NUT)
45 LB-IN
SHORT CIRCUIT CURRENT RATING
THIS PANELBOARD HAS A MAXIMUM SHORT CIRCUIT CURRENT RATING OF 100,000 AMPS RMS SYMMETRICAL, 120/240V~. THE ACTUAL RATING IS DEPENDENT ON
THE BRANCH BREAKERS INSTALLED IN THIS PANELBOARD AND THE MAIN/FEEDER BREAKER, IF ANY, INSTALLED AHEAD OF THIS PANELBOARD. THE CORRECT
MAIN BREAKER/FEEDER/MAIN BREAKER/PANELBOARD MAIN BREAKER/BRANCH BREAKER SERIES COMBINATIONS TO BE USED ARE LISTED IN THE TABULATION
BELOW. ANY CIRCUIT BREAKER INSTALLED, REPLACED, OR ADDED IN THIS PANELBOARD MUST BE MANUFACTURED BY SIEMENS (MURRAY BRAND) AND MUST
BE OF THE CORRECT TYPE AS INDICATED IN THE TABULATION BELOW. USE OF OTHER CIRCUIT BREAKERS IN THIS EQUIPMENT WILL VOID THE WARRANTY.
MAIN BREAKER
FEEDER/MAIN BREAKER BRANCH BREAKER
WHEN THE MAIN PROTECTING
THE SYSTEM IS A
AND THE BREAKER
PROTECTING THIS
PANELBOARD IS A TYPE
AND THE BRANCH
BREAKERS INSTALLED
ARE TYPE
THEN THE MAX.
SHORT CIRCUIT
CURRENT
RATING IN RMS
SYMMETRICAL AMPS,
120/240 V~ IS
MP-T
MP-T, MG, MH-T, MP-HT,
MP-MT, MP-GT, MP-HGT,
MP-ET, MP-HET, MP-AT
MP-HAT
10,000
22,000
NONE USED
65,000
‡ THIS PANELBOARD IS EITHER A MAIN LUG DEVICE THAT MAY BE CONVERTED TO MAIN BREAKER WITH THE ADDITION OF FIELD INSTALLED MAIN BREAKER KIT OR A MAIN
BREAKER DEVICE THAT MAY BE CONVERTED TO MAIN LUG WITH THE ADDITION OF MAIN LUGS. SEE ACCESSORY TABLE FOR CATALOG NUMBERS OF APPROPRIATE KITS.
SR-M1H
PANELBOARD MAIN‡
AND THE INSTALLED
MAIN BREAKER IN
THIS PANELBOARD
IS A TYPE
NONE USED
OR M1
MP-T, MP-HT, MP-MT
NONE USED
100,000
NONE USED
MP-T, MH-T, MP-HT, MP-MT,
MP-GT, MP-HGT, MP-ET,
MP-HET, MP-AT, MP-HAT
NONE USED
MP-MT
M1 OR MP-HT
NONE USED
NONE USED
NONE USED
MP-HT, MP-HET,
MP-HGT, MP-HAT
300V T FUSES - 200A MAX
NONE USED,
MP-T, MP-HT OR MP-MT
NONE USED,
M1 OR MP-T
NONE USED,
M1 OR MP-MT
NONE USED
OR M1
NONE USED OR SIEMENS BREAKER TYPES JXD2(-A), JD6(-A),
JXD6(-A), HJD6(-A), HJXD6(-A), LD6(-A), LXD6(-A), HLD6(-A),
HLXD6(-A), MD6, MXD6, HMD6, HMXD6, ND6, NXD6, HND6,
HNXD6, OR CLASS J, T, R OR L FUSES
SIEMENS BREAKER TYPES JXD2(-A), JD6(-A), JXD6(-A),
HJD6(-A), HJXD6(-A), LD6(-A), LXD6(-A), HLD6(-A), HLXD6(-A),
MD6, MXD6, HMD6, HMXD6, ND6, NXD6, HND6, HNXD6,
OR CLASS J, T, R OR L FUSES
MP-HT
NONE USED NONE USED MP-MT
MP-T, MH-T, MP-HT, MP-MT,
MP-GT, MP-HGT, MP-ET,
MP-HET, MP-AT, MP-HAT
MP-T, MH-T, MP-HT, MP-MT,
MP-GT, MP-HGT, MP-ET,
MP-HET, MP-AT, MP-HAT
LINE
EQPT GRD
EQPT GRD
NTL/E QPT GRD
NTL/E QPT GRD
23
A
EQPT GRD
EQPT GRD
EQPT GRD
NEUTRAL
BACK-FED BRKR
WHEN USED
B
1
23
2
24
1 2
24
DESCRIPTION CAT. NO.
FILLER PLATE, 1"
LX100FP
MAIN BREAKER FILLER PLATE
MBF125M
DESCRIPTION CAT. NO.
100 AMP MAIN BREAKER
125 AMP MAIN BREAKER
MBK100M
MBK125M
100-125 AMP MAIN LUG
MLK125M
ACCESSORIES
MAIN LUG / MAIN BR EAKER KITS
USE APPROPRIATE KIT FROM CHART
BELOW TO CONVERT PANEL.
BREAKER HOLD-DOWN
MBR2M
GROUND BAR KITS - USE "LX" S ERIES
TRADE SIZE CAT. NO.
1 INCH
HS100M
1-1/4 INCH
HS125M
CONDUIT HUBS
1-1/2 INCH
HS150M
2 INCH
HS200M
2-1/2 INCH
HS250M