USER MANUAL ONLINE UPS PowerMust 1000E Online LCD (1K) PowerMust 2000E Online LCD (2K) PowerMust 3000E Online LCD (3K) PowerMust 6000E Online LCD (6K) PowerMust 10000E Online LCD (10K)
Thanks for your purchasing this product! Safety instruction Please read carefully the safety instructions before you do anything to this product!
CONTENT 1. Product introduction......................................................................... 1 1.1 Functions description .................................................................... 1 1.2 Mode description ........................................................................... 2 1.3 Description of commonly used symbols........................................ 3 1.4 Front panel .................................................................................... 4 1.5 Rear panel ........
1. Product introduction 1.1 Functions description ● This product is a true online double-conversion UPS (Uninterruptible Power Supply). It provides perfect protection for critical load such as computer system. It can eliminate almost all mains power disturbances. The input AC current can be corrected to a wave following the mains voltage, so it is a high power factor system. Through the PWM control technology, the output voltage can be a pure & stable sine wave AC voltage.
1.2 Mode description ● Bypass mode Bypass mode means that the UPS provides the power through the internal bypass way to load directly without any regulation. If the controller detects the mains is abnormal, it will shut off the output to protect the load. The bypass voltage/frequency range and default output status (on/off) could be set by communication software.
1.3 Description of commonly used symbols Some or all of the following symbols may be used in this manual.
1.4 Front panel 1.4.
6KS/10KS 6K/10K 5
1.4.2 LCD display (1) LCD icon description Icon Icon name Description Mains icon It indicates the input is connected with mains, and the input power is supplied from the mains. Battery It indicates the input is connected with battery, and the input power is supplied from the battery. Bypass It indicates the UPS is in bypass mode, the load current is directly from the utility power. Inverter It indicates that the load current is supplied from utility power or battery via the inverter.
(2) LCD display in different mode LCD icon Bypass mode (output disable) ● ● Bypass mode (output enable) ● ● Line mode ● ● ● ● ● ● Battery mode ● Battery test mode ● ★ Fault mode ◇ ◇ ◇ ◇ Warning □ □ □ □ ● ● ●: Lightened constantly ★: Flashing ◇: Depended on the fault status □: Depended on the original display 1.4.3 Button There is only one button for ON/OFF/Mute function on this product. The controller can distinguish the command according to the operation time difference.
(2) UPS response to the button Original Button mode action Long-press Power off UPS response Turn on the UPS into battery mode. The internal power supply is trigged for a short time (cold status) Other press Bypass Long-press Turn on the UPS into line mode. mode Short-press Mute the buzzer if there is a warning or alarming. Long-press Turn into bypass mode. Short-press Turn into battery test mode. Battery Long-press Turn off the UPS. mode Short-press Mute the buzzer.
1.
3K 3KS ①/② Communication port (USB or RS232) ③ Mains input protection ④ Mains input power cord ⑤ Output socket ⑥ External battery terminal block 10
①/② Communication port (USB or RS232) ③ Mains input protection ④ AC input / output / External battery terminal block ⑤ Kickstand 11
1.6 Product specification 1.6.1 Model description This manual is applicable to the following models: Model name 1K 1KS 2K 2KS 3K 3KS 6K 6KS 10K 10KS Power 1000VA/700W 2000VA/1400W 3000VA/2100W 6000VA/4200W 10000VA/7000W rating Note: The model names without “S” represent standard model with internal battery. The model names with “S” represent long backup time model with external battery. 1.6.
1.6.3 Mechanical Specification 1-3K Model 1K Dimension ((W×H×D) (mm) Weight (Kg) 1KS 144x220x345 9.8 5.2 2K 2KS 190x318x369 20 10.8 3K 3KS 190x318x369 24.6 10.8 6-10K Model Dimension 6K 6KS 10K 10KS 200x735x 509 200x376x 509 200x735x 509 200x376x 509 (W×H×D) (mm) Weight (Kg) 62 26 71 26 1.6.4 Electrical Specification Model 1K Power 1000VA/ 700W 1KS 2K 2KS 2000VA/ 1400W 3K 3KS 3000VA/ 2100W 6K 6KS 10K 10KS 6000VA / 4200W 10000VA / 7000W Input Current (Max.
THD ≦4% ( Linear load ) Voltage Regulation ± 2% Overload Line mode: 60s @ 100%~130%; 1s @ > 130% Capacity Battery mode: 10s @ 100%~130%; 1s @ >130% Efficiency Line Mode 86% Battery Mode 80% 89% 83% 83% 24 48 72 VDC VDC VDC 84% 89% 88% 89% Battery & Charger @ 25℃ Total battery rating voltage 144 240 192 240 VDC VDC VDC VDC Backup Time >9min >9min >9min >9min >8min 5 5 5 5 5 Hours Hours Hours Hours Hours (Half Load) Recharge Time (to 90%) Charging Current 1A 4A 1A
1.6.5 Standards 1-3K * Safety IEC/EN 62040-1-1 * EMI Conducted Emission.......................................:IEC/EN 62040-2 Category C1 Radiated Emission......................................... :IEC/EN 62040-2 Category C1 Harmonic Current............................ :IEC/EN 61000-3-2 (Input Current≤16A) Voltage Fluctuation and Flicker........ :IEC/EN 61000-3-3 (Input Current≤16A) *EMS ESD............................................................. :IEC/EN 61000-4-2 Level 4 RS......................
1.7 Communication port The communication port is for the monitoring software. There are 2 options: RS232 or USB. There is only one option can work in the same time and same product. 1) RS232 (optional) Pin assignment and description of DB-9 connector: Pin# Definition 2 TXD (output) 3 RXD (input) 5 GND 2) USB (optional) The USB port is compliance with USB 1.1 protocol for its communication software.
2. Installation 2.1 Installation Safety Instructions You must read the following safety instructions before installation! ● Installation Personnel This product must be installed only by qualified or professional personnel accord to safety ● Installation Environment Do not install and operate the UPS when water condensation happen which may occur if the UPS is moved directly from a cold to a warm environment. The UPS must be absolutely dry before being installed and operated.
● Wiring & Grounding Installation and Wiring must be performed in accordance with the local electrical laws and regulations. The UPS must be securely grounded. If there are external UPS battery cabinets, please make sure the battery cabinets have the equipotential earth bonding to the UPS main cabinet. An appropriate switch device as backup protection for over-current or short-circuit should be provided in the input utility.
2.3 Installation steps for 1-3K standard model 1) Make sure the wire / circuit breaker / socket are enough for the current rating of UPS to avoid the hazards of electric shock and fire. 2) Make sure the mains switch in the building is cut off. 3) Make sure the UPS is not be turned on before wiring operation. 4) Turn off all load switches first before connecting the load to the UPS. 5) Make sure the protective earth ground is correct. 6) Connect the loads to the UPS through the outlet sockets.
● Prepare the external battery cable that should be able to carry the current of >50A, the cross section area should be greater than 5.26 mm 2. It is recommended to use 8 AWG wire or thicker for safety and efficiency. And battery wire color is recommended as following: + GND - Red wire Yellow/Green wire Black wire ● Connect the GND pole of external battery terminal block on the rear panel of UPS to the earth point of battery pack.
4) Prepare wires according to the following table: Wiring spec (AWG) Model Input Output 6K 12 12 6KS 12 12 10K 9 9 10KS 9 9 Battery Ground 12 12 12 9 9 9 Note 1: The cable for 6K/6KS should be able to carry the current of >40A, the cross section area should be greater than 3.31 mm 2. It is recommended to use 12 AWG wire or thicker for safety and efficiency. Note 2: The cable for 10K/10KS should be able to carry the current of >60A, the cross section area should be greater than 6.63 mm 2.
Wiring connection on the 6KS/10KS rear panel Warning: (Only for standard model) ● Make sure the UPS is not turned on before installation. The UPS must not be turned on when doing wiring operation. ● Do not try to modify the standard model to the long back up time model. Especially do not try to connect the standard internal battery to the external battery. The battery type and voltage may be different.
connected. Wrong connection may cause permanent damage of the UPS. ● Make sure the battery input wiring is correct before power on. The wire current spec, color, position, connection and conductance reliability should be checked carefully. Make sure the +/- polarity is correct, not reverse, no short circuit. ● Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection and conductance reliability should be checked carefully.
3.Operation 3.1 Operation Safety Instructions You must read the following safety instructions before operation! ● operation personnel Laymen can operate this product. ● operation warning Do not disconnect the earth conducting wire on the UPS or the building wiring terminals in any time since this would cancel the protective earth of the UPS system and all connected loads. Do not try to disassemble the original part of the UPS before turn off and disconnect it from the mains power & external battery.
3.2 Start the UPS with mains (AC source) 1) If the UPS is a long back up time model, with external battery banks, please switch on the battery breaker first; 2) If the wiring is correct, turn on the mains breaker in your building. Then the power supply inside the UPS will be started automatically, the fans will run, and the panel will display with bypass mode.
3) After the UPS is turned on to battery mode normally, the panel will display battery mode, and the buzzer will beep according to the battery level. 3.4 Connect loads to UPS After the UPS is turned on, you can switch on the loads. 1) It is recommended to switch on the load one by one. The panel will display the load level.
3.6 Discharge the batteries 1) When the UPS is in battery mode, the buzzer will beep according to different battery level. If the battery level is normal, the buzzer will beep once every 4 seconds; If the battery voltage drops to the alarming level, the buzzer will beep hurry (once every sec) to remind the user that the battery is low level and the UPS will be shutdown automatically soon. The user could switch off some non-critical loads to avoid the shutdown alarming and prolong the backup time.
3.8 Turn off the UPS with mains (AC source) 1) Firstly turn off the UPS (inverter) to bypass mode, please press the button continuously for more than 2 seconds. 2) After you press the button, the buzzer will beep once. Then the panel will display bypass mode. Note 1: If the UPS have been set to enable the bypass output, the output socket will have voltage from mains directly after you turn off the UPS (inverter) to bypass mode.
3.10 Mute the buzzer 1) To mute the buzzer, please short-press the button. If you short-press it again after the buzzer muted, the beep will be returned. 2) It is not anytime the buzzer can be muted. If it is in warning/batterylow/overload, the buzzer can’t be muted unless the trouble is solved. 3) If it is in fault mode, short-press the button could transfer the continuous beep to once-every-second. 3.
4) In the emergency case, please cut off the connection from mains / external battery / output immediately to avoid more risk or danger. 3.13 Buzzer indication summary in normal mode Operating mode Line mode Bypass mode Battery mode / Battery test mode Load level Battery level Buzzer beep once 0~100% None >100% Every 0.5 sec 0~100% Every 2 min >100% Every 0.5 sec 0~100% 0~25% Every sec 0~100% 25%~100% Every 4 sec >100% Every 0.
4. Maintenance 4.1 Maintenance Safety Instructions You must read the following safety instructions before maintenance! ● Maintenance Personnel This product must be maintained only by qualified professional personnel accord to safety instructions! ● Risk of electric shock No matter the UPS is connected to the utility power or not, the output may have electricity. The parts (battery, capacitor) inside the unit may still have hazardous voltage after turning off the UPS.