User manual
14
THD
≦4% ( Linear load )
Voltage
Regulation
± 2%
Line mode: 60s @ 100%~130%; 1s @ > 130% Overload
Capacity
Battery mode: 10s @ 100%~130%; 1s @ >130%
Efficiency
Line Mode 86% 89%
Battery Mode
80% 83% 83% 84%
89%
88%
89%
Battery & Charger @ 25℃
Total battery
rating voltage
24
VDC
48
VDC
72
VDC
144
VDC
240
VDC
192
VDC
240
VDC
Backup Time
(Half Load)
>9min
>9min
>9min
>9min
>8min
Recharge Time
(to 90%)
5
Hours
5
Hours
5
Hours
5
Hours
5
Hours
Charging Current
(Max.)
1A
4A
1A
4A
1A
4A
1A
4A
1A
4A
Discharging
Current (Max.)
44A 42A 42A 24A 39A
Rated Charging
Voltage
27.3
Vdc
54.6
Vdc
81.9
Vdc
163.8
Vdc
273
Vdc
218.4
Vdc
273
Vdc