4) Prepare wires according to the following table:
Wiring spec (AWG)
Model
Input Output Battery Ground
6K 12 12 12
6KS 12 12 12 12
10K 9 9 9
10KS 9 9 9 9
Note 1: The cable for 6K/6KS should be able to carry the current of
>40A, the cross section area should be greater than 3.31 mm
2
. It is
recommended to use 12 AWG wire or thicker for safety and
efficiency.
Note 2: The cable for 10K/10KS should be able to carry the current
of >60A, the cross section area should be greater than 6.63 mm
2
. It
is recommended to use 9 AWG wire or thicker for safety and
efficiency.
Note 3: The color of wires should be selected according to the local
electrical laws and regulations.
5) Remove the terminal block cover on the rear panel of UPS. Then
connect the wires according to the following terminal block
diagram: (Always connect the earth wire first!)
Wiring connection on the 6K/10K rear panel