3.6 Discharge the batteries
1) When the UPS is in battery mode, the buzzer will beep according to
different battery level. If the battery level is normal, the buzzer will
beep once every 4 seconds; If the battery voltage drops to the
alarming level, the buzzer will beep hurry (once every sec) to
remind the user that the battery is low level and the UPS will be
shutdown automatically soon. The user could switch off some
non-critical loads to avoid the shutdown alarming and prolong the
backup time. If have no more load to be switched off at that time,
you have to shutdown all loads as soon as possible to protect the
loads or save data. Otherwise there is the risk of data loss or load
failure.
2) In battery mode if the user dont like the buzzer noise, the beep
could be muted by short-press the button.
3) The backup time of the long backup time model is dependent on the
external battery capacity except the load capacity mainly.
4) The backup time may vary from different environment temperature
and load type.
3.7 Test the batteries
1) If you need to check the battery level or aging status when the UPS
is running on normal mode (line mode), you could short-press the
button to let the UPS transfer to battery test mode.
2) To make the system more reliable, the UPS will perform the battery
test automatically periodically. The default period is once per week.
3) The battery test could be performed by the command from monitoring
software through the communication port.
4) If the UPS enter the battery test mode, the display and buzzer
indication will be the same as the battery mode except that the
Battery icon is flashing and the mains icon lighten constantly. So you
can check the battery level at this mode.