Test from zone?
(key in number, then press “Enter’)
Figure 10: Zone Test Menu 2
Enter the number of the first zone to be tested and press [Enter]. The panel will then display Zone Test Menu 3. If, for
example, “12” is keyed in, the display would show:
Test from 12 to zone ?
(key in number, then press “Enter”)
Figure 11: Zone Test Menu 3
If “15” is keyed in, the panel would display the Walk Test Mode as follows:
Test from 12 to Zone 15
----------W----------
Figure 12: Zone Test Menu 4
The moving “W” across the lower line alternates with a “Press NO to EXIT” message.
Note: Once the display indicates the panel is in the Walk Test Mode, the display will not revert to normal. The panel will
terminate the test and sound the panel buzzer if there is no activity for a 20 minute period.
The operator may test devices within the zone parameters shown on the display. The panel responds to each test by:
Displaying an activation message on the alphanumeric display
Entering the activation in the event log
Lighting the alarm LED in the Zone/Area display
Sounding the panel buzzer
Lighting the LED at the device in alarm
After a few seconds, the panel will automatically reset and turn off the device LED. The panel allows up to one minute
for smoke devices to clear. The operator may then test the next device.
If the panel detects an alarm condition in a zone other than those being tested, all NAC devices and relays will activate
as programmed. NAC devices will continue to operate until silenced from the panel.
Terminate the Walk Test by pressing the [No] key. The display will return to the Main Menu (see Figure 13).
Note: The fourth option in the Test Menu, 4) Outputs, is not available to Control Level 2 Operators.
[ACTIVE] 1) Commission 2) Test 3) Time [1]
4) Enable 5) Disable 6) Print 7) View
Figure 13: Main Menu
Control Level 2