4.2.1 SIM-Card
A Micro SIM card is needed for the operation of the LTE modem. Push the Micro SIM card into
the slot until you hear the click. To remove the Micro SIM card push it and it will pop out.
4.2.2 USB and Display Port
The Display port and the USB port are used for debug purposes.
4.2.3 HART and Current Loop Interface
The EDGE FCR 3 does have four analogue input channels, marked as CH0- to CH3+ (Figure
28). This interface can work either as current input channel (4…20mA) or HART
1
analogue
input channel. The way how the interface is working is pre-defined in the software in context
with the device order (specification).
CAUTION
The channels do have a common grounding and no galvanic barrier to the
24VDC supply voltage of the EDGE FCR 3.
Figure 28: HART and current loop interface
IMPORTANT NOTICE
Please follow the instructions in chapter 3.6.3 Push-In Spring Power
Connector (p.32) to connect / disconnect cables from this interface
(similar handling).
1
The HART Communication Protocol (Highway Addressable Remote Transducer) is an open hybrid analogue & digital industrial
automation protocol. Its most notable advantage is that it can communicate over legacy 420mA analogue instrumentation
current loops, sharing the pair of wires used by the analogue-only host systems. HART is widely used in process and