28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 2 HI-LINE RC & HI-LINE RC HEATER/COOLER FAN CONVECTOR MODELS: 7-4, 10-6, 15-10, 20-14. INSTALLATION, OPERATING, MAINTENANCE & AFTER SALES MANUAL Product Serial Number: Please leave this manual with the end user. Part Number: 1371052 01.01.2015 ISSUE 4 heatingthroughinnovation.
8431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 3 1.0 General Information 03 2.0 Heating System Design 03 3.0 Unit Selection/Sizing 03 4.0 Location 03 5.0 Preparation 04 6.0 Fixing 04 7.0 Water Connections 05 8.0 Electrical Connection 06 9.0 Commissioning Procedure 07 10.0 Technical Data 08 11.0 Operating Instructions 09 12.0 Troubleshooting 10 13.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 4 HI-LINE RC & HI-LINE RC Heater/Cooler 03 l This unit is supplied with an infra red remote control system and has 3 operating modes: l The minimum clearance between the top of the unit and the ceiling should be 2 inches. Automatic – the desired room temperature is programmed in to the unit and the fan speed is automatically adjusted until the desired room temperature is achieved. l The minimum side clearance is 4 inches.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 5 04 HI-LINE RC & HI-LINE RC Heater/Cooler 5.0 Preparation Before proceeding with the installation, unpack the carton contents and check against the checklist below: 1. HI-LINE RC fan convector. 2. Instruction manual. 3. Fixing kit (rubber mounts and cable gland). 4. Remote control handset. 6.0 Fixing l Using the fixing dimensions below (see fig. 1), mark the fixing hole positions on the wall. l Plastic or metal anchors suitable for No.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 6 HI-LINE RC & HI-LINE RC Heater/Cooler 05 7.0 Water Connections l Connect unit to system flow and return pipes. It is recommended that two 1/2 inch isolating valves are fitted. This will enable isolation of the unit for maintenance activities. Note: External pipe-work carrying chilled water must be insulated. Use a suitable sealant as necessary to ensure that condensate does not spill or leak.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 7 06 HI-LINE RC & HI-LINE RC Heater/Cooler 8.0 Electrical Connection WARNING: This appliance must be grounded. The electrical installation must comply with state and local codes. l This unit is supplied with a factory fitted 3 core cord, 6ft in length, with moulded plug. l A suitable socket outlet with isolating switch must be available, or fitted to supply the HI-LINE.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 8 HI-LINE RC & HI-LINE RC Heater/Cooler 07 9.0 Commissioning Procedure l Fill and vent the system. l Refit outer cover. l Open both valves fully and check for leaks at pipe connections. l Switch on electrical supply. l Refit the outer case and secure using the 2 fixing screws. l Switch on electrical supply. l Check the operation of the unit by following the operating instructions.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 9 08 HI-LINE RC & HI-LINE RC Heater/Cooler 10.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 10 HI-LINE RC & HI-LINE RC Heater/Cooler 09 11.0 Operating Instructions Description that air circulation can be provided in summer for example, or that heating performance can be controlled manually. This HI-LINE unit is fitted with a control system that provides either automatic or manual control of the unit.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 11 10 HI-LINE RC & HI-LINE RC Heater/Cooler 11.0 Operating Instructions (continued...) Operation Display Manual Power off No Display Manual mode can be used for air circulation without heat or for manual control of the heating function.
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 12 HI-LINE RC & HI-LINE RC Heater/Cooler 12.0 Troubleshooting 11 (continued...
28431 HiLine manual US WEB_Layout 1 28/01/2015 13:06 Page 1 RETTIG USA, INC. (MYSON) 45 Krupp Drive, Williston, VT 05495 T: 800-698-9690, F: 802-654-7500, info@myson.com, www.mysoncomfort.com 01.01.2015 ISSUE 4 heatingthroughinnovation.