Installation Instructions

11.0 Technical Data
Performance Data 2-Pipe
Relative Humidity: Sensible cooling at 50%.
Model
Flow
(l/h)
Δ
T20
Δ
T25
Δ
T30
Δ
T35
Δ
T40
Δ
T45
Δ
T50
Heat Output (Watts) Cooling (Watts)
Condition 7-12-27
Fan
Speed
Normal 341 738 940 1146 1355 1567 1781 1997
Medium 341 989 1260 1537 1817 2101 2388 2678
Boost 341 1360 1733 2113 2499 2889 3284 3682
Normal 450 1012 1289 1572 1859 2149 2443 2739
Medium 450 1352 1723 2101 2484 2872 3265 3661
Boost 450 1892 2412 2941 3477 4020 4569 5124
Normal 600 1214 1548 1887 2231 2580 2932 3288
Medium 600 1643 2094 2553 3018 3490 3967 4448
Boost 600 2409 3070 3743 4425 5117 5815 6521
Normal 700 1428 1820 2219 2624 3034 3449 3867
Medium 700 1945 2478 3022 3573 4131 4695 5265
Boost 700 2916 3716 4531 5357 6194 7040 7894
Normal 800 1647 2099 2560 3027 3499 3977 4460
Medium 800 2246 2863 3491 4127 4772 5424 6082
Boost 800 3422 4362 5318 6288 7270 8263 9266
iV60x080
iV60x100
iV60x120
iV60x140
iV60x160
Total Sensible
707 527
1126 829
1648 1227
1011 753
1600 1178
2304 1716
1520 931
1960 1442
2918 2173
1490 1110
2320 1707
3533 2631
1729 1288
2679 1972
4147 3088
For BTUs multiply Watts by 3.412.
Performance Data 4-Pipe
Relative Humidity: Sensible cooling at 50%.
Model
Flow
(l/h)
Δ
T20
Δ
T25
Δ
T30
Δ
T35
Δ
T40
Δ
T45
Δ
T50
Heat Output (Watts) Cooling (Watts)
Condition 7-12-27
Fan
Speed
Normal 300 517 658 802 949 1097 1247 1398
Medium 300 692 882 1076 1272 1471 1672 1875
Boost 300 952 1213 1479 1749 2022 2299 2577
Normal 350 708 902 1100 1301 1504 1710 1917
Medium 350 946 1206 1471 1739 2010 2286 2563
Boost 350 1324 1688 2059 2334 2814 3198 3587
Normal 400 850 1084 1321 1562 1806 2052 2302
Medium 400 1150 1466 1787 2113 2443 2777 3114
Boost 400 1686 2149 2620 3098 3582 4071 4565
Normal 450 1000 1274 1553 1837 2124 2414 2707
Medium 450 1362 1735 2115 2501 2892 3287 3686
Boost 450 2041 2601 3172 3750 4336 4928 5526
Normal 500 1153 1469 1792 2119 2449 2784 3122
Medium 500 1572 2004 2444 2889 3340 3797 4257
Boost 500 2395 3053 3723 4402 5089 5784 6486
iV60x080
iV60x100
iV60x120
iV60x140
iV60x160
TotalFlow (l/h)
Sensible
350 672 501
350 1070 788
350 1566 1166
450 960 715
450 1520 1119
450 2189 1630
600 1444 884
600 1862 1370
600 2772 2064
700 1416 1055
700 2204 1622
700 3356 2499
800 1643 1224
800 2545 1873
800 3940 2934
For BTUs multiply Watts by 3.412.
15
iVECTOR Heater/Cooler
10.011.0
iVECTOR HEATER/COOLER
INSTALLATION, OPERATING, MAINTENANCE & AFTER SALES MANUAL
SS