Specifications
T6 Radiator Series
Before You Begin
INSPECT FOR DAMAGE
NOTE: Inspect for concealed shipping damage. Damage claims MUST be reported within 10 days of receipt.
NO EXCEPTIONS. Call 1-800-698-9690.
INSPECT FOR COMPLETENESS
Unpack the T6 carefully to avoid damage or loss of parts.
The T6 radiator includes:
Wall Brackets (2) for 16” through 63” width radiators, (3) for 70” and 78” width radiators
(2) Adapters for ½” copper compression (standard) or ½” PEX (optional)
The following are factory installed:
(2) Solid Plugs
(1) Air Vent
(1) Valve insert (Thermostatic Control optional)
APPLICATION
Myson T6 radiators must only be used in a pumped, closed loop hydronic heating system. DO NOT
INSTALL ON A STEAM OR GRAVITY HOT WATER SYSTEM. T6 radiators are designed and
constructed for a maximum working pressure of 145 PSI and no more than 230 degrees F water temperature.
Please consult national and local codes for specific restrictions that may be imposed on your installation.
Position radiators away from the circulating pump to avoid either excess pressure that could force water out
the air vent or suction which cold draw air into the system. The preferred positioning for the T6 radiator is
below a window where it can minimize downdrafts from glazed areas.
Panel radiators may be hot to the touch. Generally, the surface temperature is 10 to 12 degrees Fahrenheit
below the system water temperature. Care must be taken to consider the room occupant’s ability to sense or
understand that radiators may be hot. Should radiator surface or system water temperature be an issue, please
contact Myson at 1-800-698-9690 for information on the Myson LST radiators. LST (Low Surface
Temperature) Radiators can be a viable solution where temperature is a safety concern.
CONNECTIONS
There are two very different connection options for the T6 radiators, and the instructions are separated in the
booklet.
Bottom Center Connections: These connections must be used for the internal thermostatic valve to work. The
inlet must be the left hand connection as you face the front of the radiator. For series connection (maximum 2
GPM), HV-A or HV-S bypass valves may be used.
Side Tappings: The T6 may be connected like a conventional panel radiator. This arrangement negates the
effectiveness of the internal thermostatic valve. It will be necessary to cap the bottom center connections with
brass caps. The TRV insert should be removed and replaced with one of the plugs furnished with the radiator.
3