Specifications

T6 Radiator Series
Optional Side Valve Connections
Installation Using Side Connections
Note:
Center connections MUST be used in order for the internal distribution tubing and the built-in
thermostatic valve to function.
The T6 IVC Radiator is designed to be connected using the bottom connections. If necessary the
radiator may be installed using the side tappings although a better alternative is to use Myson’s
Select Series Radiators. For more information please contact Myson at 800-698-9690.
Preparing the T6 Radiator for side connections.
Remove the two plastic caps from the bottom center connections and discard.
Replace with nickel plated brass caps, PN: T6BCC.
T6BCC
Remove one of the blanking plugs from one of the lower side tappings.
Remove the thermostatic valve insert.
Replace with the blanking plug removed from one of the lower side tappings.
Remove the air vent assembly, separate and discard the black extension piece.
Replace the modified air vent in the top tapping. (Air vents should always be positioned on
the return side of the radiator.)
Make sure all tappings are clean and free of debris before proceeding with valve installation
shown on page 7.