Specifications
T6 Radiator Series
Optional Side Valve Connections
Installation Using Side Connections
Note:
Center connections MUST be used in order for the internal distribution tubing and the built-in
thermostatic valve to function.
The T6 IVC Radiator is designed to be connected using the bottom connections. If necessary the
radiator may be installed using the side tappings although a better alternative is to use Myson’s
Select Series Radiators. For more information please contact Myson at 800-698-9690.
Preparing the T6 Radiator for side connections.
• Remove the two plastic caps from the bottom center connections and discard.
• Replace with nickel plated brass caps, PN: T6BCC.
T6BCC
• Remove one of the blanking plugs from one of the lower side tappings.
• Remove the thermostatic valve insert.
• Replace with the blanking plug removed from one of the lower side tappings.
• Remove the air vent assembly, separate and discard the black extension piece.
• Replace the modified air vent in the top tapping. (Air vents should always be positioned on
the return side of the radiator.)
• Make sure all tappings are clean and free of debris before proceeding with valve installation
shown on page 7.
6