Specifications
Step 3 Using accepted trade practices assemble and wrench tighten fittings until
proper alignment is obtained.
Optional Side Valve Installation
Valve body stop
Copper pipe must
extend all the way to
stop. This is critical.
Applies to installation using side tappings.
Myson products are designed to be installed by professional trades people. Myson instructions
are meant to be thorough; however it is assumed that the installer has the appropriate
technical knowledge related to building codes, standard trade practices, and proper use of the
tools of the trade. Should a homeowner without such knowledge or skill take it upon
him/herself to attempt the installation, Myson will not be responsible for any damages, injuries
or unsatisfactory performance of the Myson product used.
MYSON
T6 Radiator Series
NOTE: MYSON products have BSP male and female threads. BSP threads are a straight
running thread NOT tapered like NPT. Myson Radiator Valves are designed with BSP
threads at radiator side and NPT or compression connections to system piping.
Step 1 Clean all threaded surfaces (both external and internal).
Step 2 Apply teflon tape or pipe dope to the male threads, leaving the first thread exposed.
If using pipe dope, also apply to the female threads of the radiator. Common practice
to seal BSP threads is to use heavy duty teflon tape, such as is used to seal gas pipe
fittings, or anaerobic pipe dope.
Threaded
Connection
7