Installation Guide

10
W415-0763 / A / 11.03.10
3.4 FLOOR PROTECTION
If the appliance is to be installed on top of a combustible oor, it must be placed on an approved non-
combustible hearth pad, that extends 8” beyond the appliance sides and back and 18” to the front. The
reduced clearance from the back of the appliance may result in the appliance pad terminating shorter than 8”
beyond the appliance.
K
J
J
I
MINIMUM FLOOR PROTECTION
FRONT (I) SIDES (J) BACK (K)
CANADA 18” 8” 8”
USA 16” 8” 8”
NOTE: If a section of horizontal chimney connector is used, oor protection is
required under the chimney connector and 2” beyond each side.
3.5 OUTSIDE AIR
If possible connect the air intake at the pedestal’s back or
bottom to outside air with a 4 inch (100mm) diameter fresh
air kit available at your authorized dealer / distributor.
Follow detailed instructions under “Mobile Home Outside Air”.
A (in.) B (in.)
1100 8 5/8" 9 3/4"
1400 11 1/8" 9 3/4"
1900 14 7/8" 9 3/4"
4.5"
PEDESTAL BASE
FLOOR AREA BELOW
STOVE
A"
B"
The following are signs that a fresh air kit may be required:
When there is combustion present: Wood burns poorly, smoke spills, back-draft takes place and your
chimney does not draw steadily.
In the winter there is too much condensation on the windows.
Opening a window seems to alleviate the above symptoms.
A ventilation system is installed in the house.
Other devices are present that exhaust house air.
The house has tight tting windows and/or is equipped with a well-sealed vapour barrier.
!
WARNING
IF ROOM AIR STARVATION OCCURS BECAUSE THE FRESH AIR INTAKE IS BLOCKED WITH ICE,
LEAVES, ETC., OR BECAUSE THE APPLIANCE DOOR WAS LEFT OPEN, OR DUE TO A STRONG
EXHAUST FAN OPERATING ETC., DANGEROUS FUMES AND SMOKE FROM THE OPERATING
APPLIANCE COULD BE DRAWN INTO THE ROOM.