Installation Manual
Table Of Contents
- W415-1285_Fe
- 1.0 installation overview
- 2.0 introduction
- 3.0 venting
- 4.0 installation
- 5.0 framing
- 6.0 Finishing
- 6.1 main SAFETY SCREEN removal / installation
- 6.2 end SAFETY SCREEN removal / installation (bhd4p only)
- 6.3 MAIN door removal / installation
- 6.4 END DOOR REMOVAL / installation (bhd4p only)
- 6.5 control panel removal
- 6.6 hearth pad installation
- 6.7 log placement
- 6.8 glass media installation
- 6.9 logo placement
- 7.0 wiring diagram
- 8.0 operating instructions
- 9.0 Adjustment
- 10.0 MAINTENANCE
- 11.0 replacements
- 12.0 accessories
- 13.0 troubleshooting
- 14.0 warranty
- 15.0 SERVICE HISTORY
- W415-1285_Ff
- 1.0 vue d'ensemble de l'installation
- 2.0 introduction
- 3.0 éVACUATION
- 3.1 LONGUEURS DES CONDUITS D’ÉVACUATION ET COMPOSANTS
- 3.2 INSTALLATIONS TYPIQUES D'ÉVENTS
- 3.3 INSTALLATIONS PARTICULIÈRES D'ÉVENTS
- 3.4 convertir l'Évacuation de 5/8" À 4/7"
- 3.5 EMPLACEMENTS ET DÉGAGEMENTS MINIMAUX DE LA TERMINAISON
- 3.6 CHARTE D'APPLICATION DES ÉVACUATIONS
- 3.7 LÉGENDE
- 3.8 VALEURS DU COUDE EN LONGUEURS D'ÉVENT
- 3.9 TERMINAISON HORIZONTALE
- 3.10 TERMINAISON VERTICALE
- 4.0 installation
- 5.0 ossature
- 6.0 Finitions
- 6.1 RETRAIT de l'écran de protection PRINCIPAL et l'installation
- 6.2 RETRAIT de l'écran de protection fin et l'installation (SEULEMENT bhd4p)
- 6.3 installation / enlèvement de la porte PRINCIPALE
- 6.4 Enlèvement DE LA PORTE D'EXTRÉMITÉ / INSTALLATION (SEULEMENT bhd4p)
- 6.5 enlèvement de PANNEAU DE CONTRÔLE
- 6.6 INSTALLATION des bases de protection (bHD4ST Et bHD4P SEULEMENT)
- 6.7 DISPOSITION DES BÛCHES
- 6.8 installation des BRAISES VITRIFIÉES
- 6.9 mise en place du logo
- 7.0 branchement électrique
- 8.0 instructions de fonctionnement
- 9.0 réglages
- 10.0 Entretien
- 11.0 rechanges
- 12.0 accessOires
- 13.0 dépannage
- 14.0 garantie
11
W415-1285 / F / 12.21.16
EN
3.2 TYPICAL VENT INSTALLATIONS
When venting, the horizontal run must be kept to a
maximum of 20 feet (6m). If a 20 foot (6m) horizontal
run is required, the appliance must have a minimum
vertical rise off the appliance of 57" (144.8cm).
On all horizontal vent runs, ensure that the vent pipe does not slope downward.
When terminating vertically, the vertical rise is a
minimum 36" (91.4cm) and a maximum 40 feet
(12m) above the appliance.
40 FT
(12m)
MAX
36"
(91.4cm)
MIN
16" MIN
(40.6cm)
43" (109.2cm)
MIN PLUS
RISE*
24" (61cm)
MAX
* See "VENTING" section.
38 1/4"
(97.2cm)