Installation Manual
Table Of Contents
- W415-1285_Fe
- 1.0 installation overview
- 2.0 introduction
- 3.0 venting
- 4.0 installation
- 5.0 framing
- 6.0 Finishing
- 6.1 main SAFETY SCREEN removal / installation
- 6.2 end SAFETY SCREEN removal / installation (bhd4p only)
- 6.3 MAIN door removal / installation
- 6.4 END DOOR REMOVAL / installation (bhd4p only)
- 6.5 control panel removal
- 6.6 hearth pad installation
- 6.7 log placement
- 6.8 glass media installation
- 6.9 logo placement
- 7.0 wiring diagram
- 8.0 operating instructions
- 9.0 Adjustment
- 10.0 MAINTENANCE
- 11.0 replacements
- 12.0 accessories
- 13.0 troubleshooting
- 14.0 warranty
- 15.0 SERVICE HISTORY
- W415-1285_Ff
- 1.0 vue d'ensemble de l'installation
- 2.0 introduction
- 3.0 éVACUATION
- 3.1 LONGUEURS DES CONDUITS D’ÉVACUATION ET COMPOSANTS
- 3.2 INSTALLATIONS TYPIQUES D'ÉVENTS
- 3.3 INSTALLATIONS PARTICULIÈRES D'ÉVENTS
- 3.4 convertir l'Évacuation de 5/8" À 4/7"
- 3.5 EMPLACEMENTS ET DÉGAGEMENTS MINIMAUX DE LA TERMINAISON
- 3.6 CHARTE D'APPLICATION DES ÉVACUATIONS
- 3.7 LÉGENDE
- 3.8 VALEURS DU COUDE EN LONGUEURS D'ÉVENT
- 3.9 TERMINAISON HORIZONTALE
- 3.10 TERMINAISON VERTICALE
- 4.0 installation
- 5.0 ossature
- 6.0 Finitions
- 6.1 RETRAIT de l'écran de protection PRINCIPAL et l'installation
- 6.2 RETRAIT de l'écran de protection fin et l'installation (SEULEMENT bhd4p)
- 6.3 installation / enlèvement de la porte PRINCIPALE
- 6.4 Enlèvement DE LA PORTE D'EXTRÉMITÉ / INSTALLATION (SEULEMENT bhd4p)
- 6.5 enlèvement de PANNEAU DE CONTRÔLE
- 6.6 INSTALLATION des bases de protection (bHD4ST Et bHD4P SEULEMENT)
- 6.7 DISPOSITION DES BÛCHES
- 6.8 installation des BRAISES VITRIFIÉES
- 6.9 mise en place du logo
- 7.0 branchement électrique
- 8.0 instructions de fonctionnement
- 9.0 réglages
- 10.0 Entretien
- 11.0 rechanges
- 12.0 accessOires
- 13.0 dépannage
- 14.0 garantie
18
W415-1285 / F / 12.21.16
EN
3.10 VERTICAL TERMINATION
(H
T
) < (V
T
)
Simple venting configurations.
See graph to determine the required vertical rise V
T
for the
required horizontal run H
T
.
REQUIRED
VERTICAL
RISE IN FEET
(METERS) V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
T
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet (12.2m)
Example:
V
1
= 5 FT (1.5m)
V
2
= 10 FT (3.1m)
V
T
= V
1
+ V
2
= 5 FT (1.5m) + 10 FT (3.1m) = 15 FT (4.6m)
H
1
= 3 FT (0.9m)
H
2
= 2.5 FT (0.8m)
H
R
= H
1
+ H
2
= 3FT (0.9m) + 2.5FT (0.8m) = 5.5 FT (1.7m)
H
O
= .03 (one 45° + three 90° elbows - 135°)
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
T
= H
R
+ H
O
= 5.5 FT (1.7m)+ 5.4 FT (1.m) = 10.9 FT (3.3m)
H
T
+ V
T
= 10.9 FT (3.3m)+ 15 FT (4.6m) = 25.9 FT (7.9m)
Formula 1: H
T
< V
T
10.9FT (3.3m) < 15 (4.6m)
Formula 2: H
T
+ V
T
< 40 FT (12.2m)
25.9FT (7.9m) < 40 (12.2m)
Since both formulas are met, this vent configuration is acceptable.
The shaded area within the lines represents acceptable
values for H
T
and V
T
0
5
(1.5)
10
(3.1)
15
(4.6)
20
(6.1)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
3 (0.9)
18.3A
90°
V
1
H
1
H
2
90°
90°
45°
V
2