Installation Manual
Table Of Contents
- W415-1285_Fe
- 1.0 installation overview
- 2.0 introduction
- 3.0 venting
- 4.0 installation
- 5.0 framing
- 6.0 Finishing
- 6.1 main SAFETY SCREEN removal / installation
- 6.2 end SAFETY SCREEN removal / installation (bhd4p only)
- 6.3 MAIN door removal / installation
- 6.4 END DOOR REMOVAL / installation (bhd4p only)
- 6.5 control panel removal
- 6.6 hearth pad installation
- 6.7 log placement
- 6.8 glass media installation
- 6.9 logo placement
- 7.0 wiring diagram
- 8.0 operating instructions
- 9.0 Adjustment
- 10.0 MAINTENANCE
- 11.0 replacements
- 12.0 accessories
- 13.0 troubleshooting
- 14.0 warranty
- 15.0 SERVICE HISTORY
- W415-1285_Ff
- 1.0 vue d'ensemble de l'installation
- 2.0 introduction
- 3.0 éVACUATION
- 3.1 LONGUEURS DES CONDUITS D’ÉVACUATION ET COMPOSANTS
- 3.2 INSTALLATIONS TYPIQUES D'ÉVENTS
- 3.3 INSTALLATIONS PARTICULIÈRES D'ÉVENTS
- 3.4 convertir l'Évacuation de 5/8" À 4/7"
- 3.5 EMPLACEMENTS ET DÉGAGEMENTS MINIMAUX DE LA TERMINAISON
- 3.6 CHARTE D'APPLICATION DES ÉVACUATIONS
- 3.7 LÉGENDE
- 3.8 VALEURS DU COUDE EN LONGUEURS D'ÉVENT
- 3.9 TERMINAISON HORIZONTALE
- 3.10 TERMINAISON VERTICALE
- 4.0 installation
- 5.0 ossature
- 6.0 Finitions
- 6.1 RETRAIT de l'écran de protection PRINCIPAL et l'installation
- 6.2 RETRAIT de l'écran de protection fin et l'installation (SEULEMENT bhd4p)
- 6.3 installation / enlèvement de la porte PRINCIPALE
- 6.4 Enlèvement DE LA PORTE D'EXTRÉMITÉ / INSTALLATION (SEULEMENT bhd4p)
- 6.5 enlèvement de PANNEAU DE CONTRÔLE
- 6.6 INSTALLATION des bases de protection (bHD4ST Et bHD4P SEULEMENT)
- 6.7 DISPOSITION DES BÛCHES
- 6.8 installation des BRAISES VITRIFIÉES
- 6.9 mise en place du logo
- 7.0 branchement électrique
- 8.0 instructions de fonctionnement
- 9.0 réglages
- 10.0 Entretien
- 11.0 rechanges
- 12.0 accessOires
- 13.0 dépannage
- 14.0 garantie
9
W415-1285 / F / 12.21.16
EN
3.0 VENTING
7.2C
THIS APPLIANCE USES A 5” (127mm) EXHAUST / 8” (203.2mm) AIR INTAKE VENT PIPE SYSTEM.
Refer to the section applicable to your installation.
For safe and proper operation of the appliance follow the venting instruction exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent
pipe shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions
provided for the initial installation.
NOTE: This appliance must be installed with a continuous connection of exhaust and air intake vent
pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. USE WOLF STEEL LTD. SUPPORT RING ASSEMBLY W010-0067 OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARANCE TO COMBUSTIBLES
FOR BOTH VERTICAL AND HORIZONTAL RUNS. SPACERS ARE ATTACHED TO THE INNER PIPE AT
PREDETERMINED INTERVALS TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS
REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF
EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
SAMPLE
You may reduce the appliance from 5/8" venting to 4/7" venting for horizontal and vertical rise applications.
Reducing must be done right off of the appliance and a new firestop spacer (W010-3440) will be required.










