SYMPTOM PROBLEM TEST SOLUTION
Blower does not turn on Blower high limit switch has
been activated
- Turn blower switch on, turn turbo rear burner off and
front burner to low. When blower turns on, re-adjust
burners.
Door sticking Dirt / dust adheres to the
hinges; is heated and burns
causing sticking.
- Lift door from its hinges. Lubricate with high-temp dry
graphite only.
- NOTE: Due to high temperatures that the hinges
experience, wet lubricants such as oil and WD40
will cause the hinge to seize and are therefore not
suitable.
42.3_3
White / grey lm forms. Sulphur from fuel is being
deposited on glass, logs or
combustion chamber surfaces.
- Clean the glass with a recommended gas appliance
glass cleaner.
- DO NOT CLEAN GLASS WHEN HOT.
- If deposits are not cleaned off regularly, the glass may
become permanently marked.
Exhaust fumes smelled in
room, headaches.
Appliance is spilling. - Ensure exhaust bracket gasket seal.
- Check door seal and relief ap seal.
- Check for chimney blockage.
- Check that chimney is installed to building code.
- Room is in negative pressure; increase fresh air supply.
- Check cap gasket on the ue pipe assembly.
Remote wall switch is in
’OFF’ position; main burner
comes on when gas knob
is turned to ‘ON’ position.
Wall switch is mounted upside down.
- Reverse.
Remote wall switch is grounding.
- Replace.
Remote wall switch wire is grounding.
- Check for ground (short); repair ground or replace wire.
Faulty valve. - Replace.