Installation Manual

32
EN
W415-1367 / 12.05.14
Outlet pressure can be adjusted if not
measuring 3.5” W.C. (9mb) (NG) or 10” W.C.
(25mb) (LP).
A. Pressure can be checked by removing
cap (A) using a 3/16 Allen key and
replacing it with a 1/8 NPT barb tting.
B. Place pressure gauge tube over the
tting.
C. Pressure can be adjusted by removing
cap (B) using a at screwdriver, and
adjusting the nylon plug with the same
screw driver. Turning the plug in
(clockwise) will increase the pressure.
CERAMIC
BODY
ELECTRODE
HIGH
VOLTAGE
IGNITION
CABLE
SENSOR
1/8” GAP
A
B
1/8
NPT BARB
FITTING
3.5
10
NATURAL
GAS
PROPANE
GAS
PRESSURE
GAUGE
9.0 ADJUSTMENTS
9.1 GAS PRESSURE ADJUSTMENT
AIR SHUTTER OPENINGS
LP 5/16" (7.9mm) DIA (x2)
NG 3/16" (4.7mm) DIA (x1)
It is important to periodically perform a visual check of the burner ame. Compare
them to the illustration provided.
9.2 VENTURI ADJUSTMENT
This model has an air shutter that has been factory set open according to the chart below:
Closing the air shutter will cause a more yellow ame, but can lead to carboning.
Opening the air shutter will cause a more blue ame, but can cause ame lifting
from the burner ports. The ame may not appear yellow immediately; allow 15
to 30 minutes for the nal ame color to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
NOTE: It is important that the venturi sits down tight on the ori ce.
49.3
VENTURI
BURNER
AIR
SHUTTER
OPENING
9.3 FLAME CHARACTERISTICS