4.6 240V hard wiring installation (NEFL42 / 50 / 60 / 74 / 100CHD only)
If it is necessary to hard wire this appliance. A qualified electrician must remove the cord connection and wire
the appliance directly to the household wiring. The wire and double-pole power supply breaker must be rated for
240V minimum 15 amps, maximum 20 amps.
This appliance must be electrically connected and grounded in accordance with local codes if hard wired. In
the absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the current
ANSI/NFPA 70 National Electrical Code in the United States.
!
WARNING
Turn off the appliance completely and let cool before servicing. Only a qualifi ed service person should service
and repair this electric appliance.
There are 6 wires from the appliance junction that connect to the 240V power supply (breaker panel): 1 white
(neutral), 2 yellow (heater & neutral), 1 black (power L1), 1 red (power L2), and 1 green (ground).
note:
GROUND
BLACK
BLACK
BLACK
WHITE
WHITE
WIRE NUT
WALL
SWITCH
POWER
SUPPLY
MARRET
RED
RED
RED
RED
GREEN
GREEN
THERMOSTAT
(L1)
(N)
(L1)
(N)
BLACK
YELLOW (N1)
WHITE
BLACK
WHITE
GREEN
GREEN
(L1)
(N)
(G)
WIRE NUT
RED
(L2)
RED
(L2)
(L1)
(N)
(G)
240V
WHITE (N)
WHITE (N)
BLACK (L1)
BLACK (L1)
GREEN (G)
GREEN (G)
120V
1. Remove the securing screw from the electrical cover plate, located on the rear left side of the appliance.
2. Loosen the securing screw from the terminal block to remove the cord from the terminal block.
3. Add an electrical box connector and feed the supply wires through the 7/8” (22mm) hole from the terminal
block.
4. Insert White (N) wire from power supply to the designated (N) slots in the terminal block. Secure by tightening
the screws on the (N) slots.
5. Repeat step 4 with Black (L1) and Green (G), securing them to their designated slots in the terminal block.
6. Re-install cover plate.