Installation Manual
Table Of Contents
- W415-1642_Ae
- W415-1642_Af
W415-1642 / A / 08.25.16
12
EN
3.3.2 HEARTH EXTENSION
18" (457mm)
6
1
/2"
(165mm)
70"
(1778mm)
70"
(1778mm)
20" (508mm)
12"
(305mm)
An acceptable 61½" (1562mm) x 20" (508mm) non-combustible
(ie: brick, stone or ceramic tile) hearth extension must be installed.
Hearth must extend 20" (508mm) in front of the faceplate when
it is not elevated (see local building codes). Hearth must extend
a minimum of 12" (305mm) to both sides of the appliance [70"
(1778mm)].
Hearth must be a minimum of 1" (25mm) thick cement board (or
equivalent) plus ¼" (6.4mm) ceramic tile.
Ensure that the gap between the appliance and a combustible
hearth extension is sealed with sand/cement grout or covered with
a metal strip (or both) to prevent sparks and embers from falling
into this area.
HEARTH EXTENSION
Elevated hearths must be constructed of noncombustible
materials such as cement blocks or bricks.
While the appliance can be installed directly on the floor, a non-
combustible hearth extension is required in front of the appliance,
that must not be built higher than the bottom of the appliance faceplate. It may therefore be advisable to build
the appliance on a raised platform.
Hearths raised minimum 6 ½" (165mm) must extend a minimum of 18" (457mm).
EMBER STRIP
SEE HEARTH
EXAMPLES
A raised hearth together with the appliance built on a raised platform is recommended for easier wood loading
and fire viewing.