Installation Manual
Table Of Contents
- W415-1642_Ae
- W415-1642_Af
W415-1642 / A / 08.25.16
18
EN
4.5 INSTALLING FLASHING AND STORM COLLAR
88.1A
Remove the nails from the shingles above and to the sides of
the chimney. Place the fl ashing over the chimney pipe and slide
underneath the sides and upper edge of the shingles. Ensure that
the chimney pipe is properly centered within the fl ashing, giving
a 3/4” (19.1mm) margin all around. Fasten to the roof on the top
and sides. DO NOT NAIL through the lower portion of the fl ashing.
Make weather-tight by sealing with caulking. Where possible, cover
the sides and top edges of the fl ashing with roo ng material. Apply
waterproof caulking, provided with the fl ashing, around the chimney,
1” (25.4mm) above the top of the fl ashing and push the storm collar
down into the caulking. Insert a rain cap onto the top of the last
chimney section.
RAIN CAP
CAULKING
STORM COLLAR
WEATHER
SEALANT
FLASHING
4.6 AIR COOLED CHIMNEY INSTALLATION
A. Install the base plate starter collar. Affix using the four screws.
B. Install air housing to the appliance and connect to liner.
C. Follow the chimney manufacturer's instructions for installing
the chimney.
AIR HOUSING
Use DuraVent DuraChimney II brand of air cooled chimney.
CHIMNEY COMPONENTS DuraChimney II
12" (305mm) Chimney Section 10DAC-12
48" (1219mm) Chimney Section 10DAC-48
36" (914mm) Chimney Section 10DAC-36
15° Elbow 10DAC-E15
Chase Top Flashing 10DAC-CTF
Chimney Cap 10DAC-VC
Firestop / Radiation Shield 10DAC-RRS
CHIMNEY COMPONENTS WOLF STEEL
Air Housing* NZAC10KT
Anchor Plate 10DAC-Ap
NOTE: M&G DuraVent DuraChimney II is allowed for use
on this product.
AIR HOUSING
4" (102mm)
LINER
NOTE: Follow the chimney manufacturer's instructions for
installing the chimney.
NOTE: Use 111kt outside air kit to connect to air housing.
Maximum length of 4" (101.5 mm) liner is 20' (6 m). If greater
length is required then increase the liner diameter to 6"
(152.4mm)
*Required for DuraChimney II