installation planning
2.4 minimum clearance to combustibles
!
WARNING
• Do not install into any area having less than 7 feet (2.1m) (ceiling to appliance bottom, excluding hearth height).
CONFIGURATION
SIDE WALL
(A)
SIDE WALL
TO FLUE
(B)
BACK
WALL (C)
BACK
WALL TO
FLUE (D)
CEILING
(E)
With T.H.S.
Straight with single wall pipe
16 1/4”
(41.2cm)
27 1/2”
(69.8cm)
9 1/2”
(24.1cm)
11”
(27.9cm)
84”
(213.3cm)
Straight with double wall pipe
6 1/2”
(16.5cm)
7 1/2”
(19cm)
Through the wall with single wall pipe
9 1/2”
(24.1cm)
11”
(27.9cm)
Through the wall with double wall pipe
6 1/2”
(16.5cm)
7 1/2”
(19cm)
Without T.H.S.
Straight with single wall pipe *
16 1/4”
(41.2cm)
27 1/2”
(69.8cm)
14 1/2”
(36.8cm)
16”
(40.6cm)
96”
(243.8cm)
Straight with double wall pipe
*
12 1/2”
(31.7cm)
13 1/2”
(34.2cm)
Through the wall with single wall pipe
*
14 1/2”
(36.8cm)
16”
(40.6cm)
Through the wall with double wall pipe *
12 1/2”
(31.7cm)
13 1/2”
(34.2cm)
CONFIGURATION SIDE WALL
SIDE WALL
TO FLUE
BACK
WALL
BACK
WALL TO
FLUE
CEILING
With
T.H.S.
Corner (F)
4”
(10.1cm)
14 1/4”
(36.1cm)
4”
(10.1cm)
14 1/4”
(36.1cm)
84”
(213.3cm)
Without
T.H.S.
Corner (F) *
6”
(15.2cm)
16 1/4”
(41.3cm)
6”
(15.2cm)
16 1/4”
(41.2cm)
96”
(243.8cm)
BACK WALL
B
SIDE WALL
A
BACK WALL
C
SIDE WALL
F
K
J
J
I
D
E
E
BACK WALL
B
SIDE WALL
A
BACK WALL
C
SIDE WALL
F
K
J
J
I
D
E
E
E
BACK WALL
B
SIDE WALL
A
BACK WALL
C
SIDE WALL
F
K
J
J
I
D
E
E
F
F
Clearances can be reduced with shielding acceptable to
local authorities. Reduced installation must comply with
NFPA 211 or CAN/CSA-B365.
* The top heat shield (T.H.S) may be removed if desired
(Fig. 2-3); however, this will increase clearances to
combustibles. Please read the above table carefully.
Fig. 2-3
Top Heat
Shield