Electronic Accessory User Manual

cFP-RLY-421 12 ni.com
Physical
Indicators .......................................... Green POWER and
READY indicators, 8 green
output state indicators
Weight
cFP-RLY-421.............................. 130 g (4.5 oz)
Power Requirements
Power from network module ............ 1,700 mW
Isolation Voltage
Maximum isolation voltage .............. 250 V
rms
Channel-to-channel isolation............ No isolation between
channels
Transient overvoltage........................ 2,300 V
rms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... 40 to 60 °C
Storage temperature.......................... –55 to 85 °C
Humidity ........................................... 10 to 90% RH,
noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered
Pollution Degree ............................... 2
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64).............................. 10–500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................ 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations