NI UES-3880 Hardware Installation Guide First Edition, Sept 2007 P/N: 1802003080110
Overview The NI UES-3880 is a smart Ethernet switch that provides an economical solution for your Ethernet connections. As an added bonus, the built-in smart alarm function helps system maintainers monitor the health of your Ethernet network. The NI UES-3880 has a wide operating temperature range of -40 to 75ºC, and is designed to withstand a high degree of vibration and shock.
Panel Layout Front Panel View 2 1. 5 6 7 2. Grounding screw Terminal block for power inputs PWR1/PWR2 and relay output 11 8 3. Heat dissipation orifices 4. DIP switches 5. Power input PWR1 LED 6. Power input PWR2 LED 7. Fault LED 9 8. 10/100BaseT(X) Port 10 9. TP port’s 100 Mbps LED 10. TP port’s 10 Mbps LED Top Panel View 11. Model Name 12. Screw holes for wall mounting kit 1 V2+ 13.
Mounting Dimensions (unit = mm) 21.00 30.00 54.00 9.50 Side View 135.00 (unit = mm) 105.00 25.71 15.10 13.10 25.40 + 39.37 + 13.90 18.20 13.90 9.75 3.50 + + 6 + + 6.00 26 + 3.50 + 10 + + 6.00 10 + + 5 30.50 7.75 7.75 13 18 13 23.15 46.77 135.
DIN-rail Mounting The aluminum DIN-rail attachment plate should already be fixed to the back panel of the switch when you take it out of the box. If you need to reattach the DIN-rail attachment plate, make sure the stiff metal spring is situated towards the top, as shown in the figures below. STEP 1: Insert the top of the DIN-rail into the slot just below the stiff metal spring. STEP 2: The DIN-rail attachment unit will snap into place as shown below.
STEP 3: Once the screws are fixed in the wall, insert the four screw heads through the large parts of the keyhole-shaped apertures, and then slide the NI UES-3880 downwards, as indicated. Tighten the four screws for added stability. ⇒ Wiring Requirements WARNING Do not disconnect modules or wires unless the power supply has been switched off or the area is known to be non-hazardous. The devices may only be connected to the supply voltage shown on the type plate.
You should also pay attention to the following items: y Use separate paths to route wiring for power and devices. If power wiring and device wiring paths must cross, make sure the wires are perpendicular at the intersection point. y NOTE: Do not run signal or communications wiring and power wiring in the same wire conduit. To avoid interference, wires with different signal characteristics should be routed separately.
STEP 1: Insert the negative/positive DC wires into the V-/V+ terminals. Top View STEP 2: To keep the DC wires from pulling loose, use a small flat-blade screwdriver to tighten the wire-clamp screws on the front of the terminal block connector. Front View STEP 3: Insert the plastic terminal block connector prongs into the terminal block receptor, which is located on the NI UES-3880’s top panel.
RJ45 (8-pin) to RJ45 (8-pin) Cross-Over Cable Wiring Cross-Over Cable Switch Port (NIC Port) RJ45 Plug Pin 1 RJ45 Connector (Rx+) (Rx-) (Tx+) (Tx-) Switch Port (NIC Port) RJ45 Connector Cable Wiring Tx+ TxRx+ Rx- 3 6 1 2 1 2 3 6 Rx+ RxTx+ Tx- (Tx+) (Tx-) (Rx+) (Rx-) Redundant Power Inputs Both power inputs can be connected simultaneously to live DC power sources. If one power source fails, the other live source acts as a backup, and automatically supplies all of the NI UES-3880’s power needs.
LED Indicators The front panel of the NI Switch contains several LED indicators. The function of each LED is described in the table below. LED PWR1 PWR2 FAULT 10M 100M Color State On Off Power is not being supplied to power input PWR1 On Power is being supplied to power input PWR2 Off Power is not being supplied to power input PWR2 On When the corresponding PORT alarm is enabled, and the port’s link is inactive.
where it is not needed. Packets that are used in maintaining the operation of the network (such as the occasional multi-cast packet) are forwarded to all ports. The NI UES-3880 operates in the store-and-forward switching mode, which eliminates bad packets and enables peak performance to be achieved when there is heavy traffic on the network. Switching and Address Learning The NI UES-3880 has an address table that can hold up to 1K node addresses, which makes it suitable for use with large networks.
Specifications Technology Standards Forward and Filtering Rate Packet Buffer Memory Processing Type Address Table Size Latency Interface RJ45 Ports LED Indicators DIP Switch Alarm Contact Power Input Voltage Input Current @ 24VDC Connection Overload Current Protection Reverse Polarity Protection Mechanical Casing Dimensions Weight Installation Environmental Operating Temperature Storage Temperature Ambient Relative Humidity Regulatory Approvals Safety Hazardous Location EMI EMS Operating Shock Operating Vib
Technical Support and Professional Services Visit the following sections of the National Instruments Web site at ni.com for technical support and professional services: • Support— Online technical support resources at ni.
Worldwide Technical Support and Product Information ni.