2-4 Chapter 2: Installing the Hardware Infrastructure
General Layout Instructions
The cable length between any two devices (10/100Base-T
compatible Ethernet hub to CBS or CBS to CBS) cannot exceed 100
m (328 ft.).
The maximum number of Ethernet levels beyond the primary CBS
is three (3).
The maximum total cable length is as follows:
Cable Maximum Cable Length
Ethernet (primary CBS to last CBS in chain) 300 m (984 ft.)
Power supply to last CBS in the chain 162 m (532 ft.)
Use only NCR authorized communication cable.
Communication cables must be secure and locked into their
connectors.
The maximum number of CBSs per store is 85.
If the communication cable is routed through an exposed area, such
as up the side of a wall, across the top of a freezer where
merchandised is stacked, or in an elevator shaft, it must be in a
conduit and the conduit must be connected to the building ground.
The minimum distance between a communication cable and a
fluorescent, neon, or incandescent light is 30 cm (12 in.).
Minimum distance between a transmit or receive antenna and a
neon light is 2.43 m (8 ft.).
All communication cable connections must be protected from
electrical and mechanical deterioration. The deterioration of
communication cable connections due to corrosion or electrolysis,
especially in a humid or corrosive atmosphere, may result in
electrical noise.